Wiring section from the regulator to the battery:
Table for Copper cables (Cu).
Model
Batería (V) 0-5m
(mm
2
)
0-5m
(AWG)
5m-10m
(mm
2
)
5m-10m
(AWG)
Bornay 13+
12
50
1/0
95
4/0
Bornay 13+
24
35
2
70
2/0
Bornay 13+
48
25
3
50
1/0
Bornay 25.2+ *
12
50
1/0
120
5/0
Bornay 25.2+
24
50
1/0
95
4/0
Bornay 25.2+
48
35
2
70
2/0
Bornay 25.3+ *
12
50
1/0
120
5/0
Bornay 25.3+ **
24
50
1/0
95
4/0
Bornay 25.3+
48
50
1/0
95
4/0
Cables longer than 10m are not recommended for the connection between
the regulator and the batteries. If, for some reason, it is required to install
longer cables, it must be approved by Bornay.