User’s Manual
19
The control wiring must be connected to the utility side of the line reactor
and is phase sensitive.
DANGER!
The AC control wiring to the 150A, 225A, and 300A units is phase sensitive.
If the AC control wiring is not in phase with power wiring catastrophic
damage to equipment will result.
3.4.1.3.
DC
B
US
I
NPUT
The DC bus input may be connected to the DC bus of a single AC drive
or to a common DC bus. If a reactor or choke are being used in the bus,
make sure the actual connection is in parallel with filter capacitors of the
drive/inverter.
DANGER!
Never attach the DC bus input of the M3645P to braking terminals on the AC
drive, commonly marked “BR”. These terminals are intended for use with an
external resistor, and are not directly connected to the bus filter capacitors of
the drive. Damage may occur if these terminals are used.
Please refer to your AC drive manual or AC drive technical support department
for assistance with this connection.
3.4.1.4.
G
ROUNDING
Using the ground stud provided, ground the chassis in accordance with
local codes. Typically, the wire gauge will be the same as is used to
ground the attached drive.
Table 3-2: Power Terminal Specifications - 30 Amp Unit
– M10 Chassis
T
ERMINALS
F
UNCTION
E
LECTRICAL
R
ATINGS
W
IRE
S
IZE
M
INIMUM
W
IRE
S
IZE
M
AXIMUM
T
ORQUE
L1, L2, L3
AC line outputs
30 A
8 AWG
2 AWG
32 lb-in
DC+, DC-
DC bus inputs
30 A
8 AWG
2 AWG
32 lb-in
GND
Ground
10 AWG
1/0
50 lb-in
Table 3-3: Power Terminal Specifications - 50 Amp Unit
– M11 Chassis
T
ERMINALS
F
UNCTION
E
LECTRICAL
R
ATINGS
W
IRE
S
IZE
M
INIMUM
W
IRE
S
IZE
M
AXIMUM
T
ORQUE
L1, L2, L3
AC line outputs
50 A
4 AWG
2/0
120 lb-in
DC+, DC-
DC bus inputs
50 A
4 AWG
2/0
120 lb-in
GND
Ground
8 AWG
1/0
50 lb-in
Table 3-4: Power Terminal Specifications - 100 Amp Unit
– M12 Chassis
T
ERMINALS
F
UNCTION
E
LECTRICAL
R
ATINGS
W
IRE
S
IZE
M
INIMUM
W
IRE
S
IZE
M
AXIMUM
T
ORQUE
L1, L2, L3
AC line outputs
100 A
1 AWG
2/0
120 lb-in
DC+, DC-
DC bus inputs
100 A
1 AWG
2/0
120 lb-in
Summary of Contents for M3645P
Page 14: ...M3645P 14 This page intentionally left blank ...
Page 22: ...M3645P 22 Figure 3 5 M3645P 150A 225A and 300A Connection Locations ...
Page 27: ...User s Manual 27 Figure 3 9 M3645P 150A 225A and 300A Power Wiring ...
Page 30: ...M3645P 30 This page intentionally left blank ...
Page 45: ...User s Manual 45 Figure 6 2 M3645P M11 Chassis Dimensional Outline ...
Page 46: ...M3645P 46 Figure 6 3 M3645P M12 Chassis Dimensional Outline ...
Page 47: ...User s Manual 47 Figure 6 4 M3645P M15 Dimensional Outline ...
Page 48: ...M3645P 48 Figure 6 5 M3645 M15 Line Reactor Dimensional Outline ...
Page 50: ...M3645P 50 6 7 BLOCK DIAGRAM Figure 6 7 Typical Customer Application ...
Page 53: ...User s Manual 53 NOTES ...
Page 54: ...M3645P 54 ...
Page 55: ......