M3645P
18
▪
Where possible, minimize the wire length between the Power Supply and
the Drive. The wire length should not exceed 10 feet.
▪
Avoid routing and bundling the Power Supply AC/DC wiring with the Drive
AC PWM motor output wiring.
3.4.1.1.
3-
PHASE
AC
I
NPUT
Do not install chokes or reactors between the power supply and the power
source. M3645P has an internal 5% line reactor.
If an isolation transformer is to be used, the transformer should meet the
ratings shown in Table 3-1.
Table 3-1: Transformer Ratings
Model
Minimum kVA
Maximum
Impedance
L30
13.5 kVA
5.0%
E30
23 kVA
2.9%
H30
26.5 kVA
2.5%
C30
33 kVA
2.0%
L50
22 kVA
6.0%
E50
38 kVA
3.4%
H50
44 kVA
3.0%
C50
55 kVA
2.4%
L100
44 kVA
6.3%
E100
75.5 kVA
3.6%
H100
87.5 kVA
3.1%
C100
109.5 kVA
2.5%
L150
75 kVA
5.0%
E150
125 kVA
6.0%
H150
150 kVA
4.0%
L225
100 kVA
5.0%
E225
170 kVA
6.0 %
H225
200 kVA
4.0%
L300
131 kVA
4.4%
E300
226.5 kVA
2.5%
H300
262 kVA
2.2%
Do not connect to a generator. For further details, contact Bonitron.
The AC line connections should have short-circuit current protection.
Recommended fuses are listed in Section 6.5.
3.4.1.2.
I
NTER
-M
ODULE
W
IRING FOR
150A,
225A,
AND
300A
U
NITS
For M3645 rated for 150A, 225A, and 300A an individual line reactor
must be used in front of each line regen module. See Figure 3-10 for
wiring diagram.
The user must wire both the control AC wiring from the line reactor to
the line regen module.
Summary of Contents for M3645P
Page 14: ...M3645P 14 This page intentionally left blank ...
Page 22: ...M3645P 22 Figure 3 5 M3645P 150A 225A and 300A Connection Locations ...
Page 27: ...User s Manual 27 Figure 3 9 M3645P 150A 225A and 300A Power Wiring ...
Page 30: ...M3645P 30 This page intentionally left blank ...
Page 45: ...User s Manual 45 Figure 6 2 M3645P M11 Chassis Dimensional Outline ...
Page 46: ...M3645P 46 Figure 6 3 M3645P M12 Chassis Dimensional Outline ...
Page 47: ...User s Manual 47 Figure 6 4 M3645P M15 Dimensional Outline ...
Page 48: ...M3645P 48 Figure 6 5 M3645 M15 Line Reactor Dimensional Outline ...
Page 50: ...M3645P 50 6 7 BLOCK DIAGRAM Figure 6 7 Typical Customer Application ...
Page 53: ...User s Manual 53 NOTES ...
Page 54: ...M3645P 54 ...
Page 55: ......