![Bongioanni Multidea Evo 100 Installation And Maintenance Instructions Manual Download Page 51](http://html.mh-extra.com/html/bongioanni/multidea-evo-100/multidea-evo-100_installation-and-maintenance-instructions-manual_2787069051.webp)
eco
esc
menu
ok
Lunedi, 24. Settembre 2012
09.37
If these do not correspond, gradually adjust the MAX gas adjuster screw on the gas valve until the analyser shows the
correct combustion values.
+
-
+
-
Multidea Evo 60 gas valve
MAX
gas
MIN
gas
Multidea Evo 100 and 115 gas valve
- Press
A
to reduce power to 0% (see section “MANUAL
TEST function” page 47). This sets the heating unit to
operate at Minimum Capacity.
- Measure the gas flow rate, taking into account any relevant
corrective factors.
- Use the analyser to take CO
2
and CO readings.
Compare the readings with those of the table on the previous
page.
If these do not correspond, gradually adjust the MIN gas adjuster
screw on the gas valve until the analyser shows the correct
combustion values.
Press
C
to deactivate the MANUAL TEST function.
If necessary, make adjustments both at the maximum and
minimum values.
b
WARNINGS
•
If the control values are not accessible, check that:
- the flue extraction ducts or air intake ducts are not obstructed;
- the gas pressure is not lower than 18 mbar (G20) or 25 mbar (G31);
- the blower RPM is correct.
+
-
+
-
MAX
gas
MIN
gas