TECHNICIAN
MENU
Keys
Sub-menu
Keys
Sub-menu
Keys
Lines
Keys
Factory
settings
Field
5. USER
SETTINGS
C
1. Heating
C
1. CH setpoint
C
1. CH setpoint
C
75°C
20 - 85°C
D
B
D
D
2. Outside
temperature for
CH off
C
OFF
OFF /
7 - 25°C
2. ECO setpoint
reduction
C
--->
--->
50°C
0 - 50°C
D
3. Scheduler set
C
1. Enable/disable on
board scheduler
C
Enabled
Enabled/
disabled
D
2. Scheduler set
C
Monday
week days
D
2. DHW settings
C
1. DHW setpoint
C
--->
--->
80°C
30 - 85°C
D
2. ECO setpoint
reduction
C
--->
--->
20°C
0 - 50°C
D
3. Scheduler set
C
1. Enable/disable on
board scheduler
C
Enabled
Enabled/
disabled
D
2. Scheduler set
C
Monday
week days
D
3. Holiday settings
C
1. CH holiday
setpoint
C
--->
--->
20°C
20 - 85°C
D
2. DHW holiday
setpoint
C
--->
--->
30°C
30 - 85°C
6.CASCADE
C
1. Cascade set
C
1. Cascade switch
delay
C
--->
--->
60s
0÷255 s
D
B
D
2. Cascade min
power
C
--->
--->
14%
0÷100%
D
3. Single burner
power
C
--->
--->
depending
on heating
appliance
0÷2550kW
D
4. Boiler for DHW
C
--->
--->
0
0÷6
D
5. PI loop period
C
--->
--->
4s
1÷15 s
D
6. Burner water
flow delay
C
--->
--->
30s
0÷255 s
D
7. Different boiler
size
C
--->
--->
Disabled
Enabled/
disabled
D
8. Cascade pump
speed max.
C
--->
--->
100%
15÷100%
D
9. Cascade pump
speed min.
C
--->
--->
30%
15÷100%
D
2. Cascade info
C
--->
--->
--->
--->
Read only
D
3. Cascade
autodetect
C
--->
--->
--->
--->
-----
-----
- 35
-
INST
ALLA
TION