BOILER OPERATING AND MAINTENANCE Guidance for the User
The only operation that the end user can carry out on the boiler are as follows:
-
check the presence of water in the boiler and installation (once a week at least)
-
Reset of circulating pump, when fitted, after a period of inactivity of more than 15 days.
[Switch off the boiler, unscrew the pump screw (it is normal that a small quantity of water
overflows) and release the disk wheel by means of a screw driver].
-
Reset of limit thermostat when pilot burner does not stay alight after ignition (IDEA boi-
lers with electric ignition).
-
Reset of limit thermostat and of boiler lockout button, when boiler is tripped (IDEA boi-
lers with electronic ignition).
-
In case of doubts, or should the boiler go to lockout for more than three times, then apply
to a Qualified Gas Service Engineer.
3
CHECKING THE FLUE THERMOSTAT
2.7.4
It is strongly recommended that the efficient and safe operation of the flue thermostat is
checked as follows:
-
temporarily obstruct the flue above the darught diverter with an insulating material
capable of enduring temperature of approx. 300°C
-
open all the windows of boiler room to ensure air circulation before lighting the boi-
ler
-
the burner should stop within 2 minutes and the signal lamp indicating chimney
should light (if not, flue thermostat should be replaced)
-
turn off the main switch, turn off gas supply at the gas service cock
-
refit the flue duct
-
remove the temporary flue obstruction
-
wait until the thermostat phial has cooled (approx. 10 minutes after intervention)
-
reset the flue thermostat
-
re-light the boiler.
SHOULD THE FLUE THERMOSTAT SIGNAL LAMP LIGHT AT ANY TIME
DURING NORMAL OPERATION, CHECK THE CHIMNEY DRAUGHT.
SWITCHING THE BOILER ON
-
Open gas cock
-
turn main switch ON
-
Adjust boiler thermostat dial to the minimal temperature.
3.1