6
The last version of
UProg
Configuration Tool as well as additional information about the
module can be downloaded from the Bolid website at the address of
www.bolid.com
.
2 INSTRUCTIONS
2.1 Safety Precautions
2.1.1 There are potential hazard circuits within the module, and their connecting contacts
are covered by the electrically insulating cover.
2.1.2 Do SHUT OFF the device power before mounting, wiring, or maintaining the module.
2.1.3 Mounting and maintaining the module MUST be performed by qualified engineers.
2.2 Preparing for Using
2.2.1 If necessary, change the module’s network address. The address of the module
must not be the same as an address of any device connected to the same RS-485 bus.
2.2.2 Adjust other configuration parameters of the module to meet the specific
requirements to the module.
2.2.3 Mount the module on the wall or within a cabinet in accordance with its Installation
Manual (the module is to be mount closely to executive devices at places protected against
atmospheric fallouts, mechanical damage, and unauthorized access). If the module is
mounted in unprotected premises, attach it at a height of at least 2.2 m above the floor.
2.2.4 Wire the module as shown in Annex B.
2.2.4.1 If the module and the network controller are connected to various power supplies,
couple their circuits “0V”.
2.2.4.2 Unless the module is the last device (the furthest from the network controller),
remove the jumper XP2.
2.3 Using the Module
2.3.1 The circuits the module should switch are connected to it in accordance with the
following.
The circuits which unauthorized closing is prohibited even in case of power shut off, must
be connected to normally open relay contacts (“NO” and “COM”).
The circuits, which unauthorized opening is prohibited even in case of power shut off,
must be connected to normally closed relay contacts (“N
С” and “COM”).
To close NO relay contacts and to open NC contacts, use the executive program Switch
On (1) or Switch On for a Time (3), with the initial condition for the relay being equal to “Off”.
3 MAINTENANCE
3.1 General
To make sure your S2000-SP1 mod.01 module keeps proper operability, it must be
inspected by a competent specialist at least on receipt and annually. The inspection algorithm
shall include:
–
Visual checking the S2000-SP1 mod.01 against contaminations and mechanical
damage;
–
Verifying the S2000-SP1 mod.01 for secure mounting and wire connection conditions;
–
Inspection of the S2000-SP1 mod.01 operability in accordance with techniques shown
below.