2.3  If the module is to be mounted within unprotected premises, it is recommended to mount it 
at a height of minimum 2.2 m above the floor. 

 

Figure 1. Overall and Mounting Dimensions of the Module 

3  MOUNTING THE MODULE 

3.1 Mounting on a Wall 

3.1.1  Please  ensure  that  the  wall  the 
module  is  to  be  mounted  to  is  solid,  flat, 
clean, and dry. 
3.1.2  Attach  the  module  to  the  wall  in 
accordance with the Variant 1 or Variant 2 
below. 

3.1.3  Variant  1.  Apply  the  Mounting 
Pattern  (page 7)  to  the  wall.  Drill  three 
holes (A, B and C or D). 
3.1.4  Insert  wall  plugs  to  the  holes  and 
screw  provided  woodscrews  to  the  two 
upper  holes  so  that  a  distance  between  a 
screw head and the wall is about 7 mm. 
3.1.5  Remove  the  module  cover  as 
shown in Figure 2. 
3.1.6  Hang  the  module  on  the  two 
screws.  Screw  the  third  screw  into  the 
bottom  mounting  hole  and  fasten  the 
module to the wall. 

3.1.7  Variant 2. Apply the Mounting 
Pattern (page 7) to the wall. Drill three 
holes (A, B and C or D)

.

 

 

Figure 2. Opening the front cover 

3.1.8  Insert wall plugs to the holes. 

Push the top end of 

the front cover down 

by your thumbs 

Slide the 

cover 

forward

 

Unscrew the 

screw fixing the 

cover 

Summary of Contents for S2000-SP1 ORION ISS

Page 1: ...can also be downloaded from the website of the Bolid Company at the address of www bolid com in the Products Section 1 SAFETY PRECAUTIONS There are no potential hazard circuits within the module Do SHUT OFF the device power before mounting wiring or maintaining the module Mounting and maintaining the module MUST be performed by qualified engineers 2 MOUNTING THE MODULE 2 1 The module is to be moun...

Page 2: ...Apply the Mounting Pattern page 7 to the wall Drill three holes A B and C or D 3 1 4 Insert wall plugs to the holes and screw provided woodscrews to the two upper holes so that a distance between a screw head and the wall is about 7 mm 3 1 5 Remove the module cover as shown in Figure 2 3 1 6 Hang the module on the two screws Screw the third screw into the bottom mounting hole and fasten the module...

Page 3: ...ve the ХР2 jumper from the module PCB see Figure 4 4 1 3 If the module the console or other Orion system devices connected to the RS 485 interface bus are supplied with power by different power supplies couple their 0V circuits 4 2 Connecting Executive Devices 4 2 1 Connect normally open contacts of a relay NO and COM to the circuits which unauthorized closing is prohibited even upon power failure...

Page 4: ...as shown in Figure 6 Figure 4 S2000 SP1 Wiring Diagram Tamper Switch Jumper to connect EOL resistor 620 Ω ХР2 ORION Pro Software S2000M Console S2000 Console А В NC1 0V U1 0V U2 COM2 NO1 COM1 RS 485 NO2 NC2 To executive devices ХТ1 COM4 NO4 NC3 COM3 NO3 NC4 RIP 12 RIP 24 Interface Bus to connect to the ORION system 0V 12V 24V Main Power Supply RIP 12 RIP 24 0V 12V 24V Backup Optional Power Supply ...

Page 5: ...5 5 3 The module s READY indicator shall be lit steady in green within 5 s 5 5 4 Within a minute since powering on the console it shall display a message about detecting a device with the network address assigned to the module factory value of the module address is 127 Figure 5 shows the display of the S2000M console with the relevant message 5 5 5 If several messages accumulated by the module hav...

Page 6: ... installed Orion Pro software it should be assigned to a unique network address and be set properly see the Instruction Manual for the S2000 SP1 ZAO NVP Bolid 4 Pionerskaya Str Korolev 141070 Moscow Region Russia Phone fax 7 495 775 7155 Email info bolid ru overseas bolid com www bolid com 1 Place cover tabs under the hooks of the module base 2 Turn the cover until clicks specifically Fasten with ...

Page 7: ...www bolid com S2000 SP1 ver 1 56 INSTALLATION MANUAL rev 0 7 Figure 7 Mounting Pattern ...

Page 8: ...o any implied warranty of merchantability must be brought within 12 months from date of original purchase In no case shall seller be liable to anyone for any consequential or incidental damages for breach of this or any other warranty express or implied or upon any other basis of liability whatsoever even if the loss or damage is caused by the seller s own negligence or fault Some countries do not...