S2000-IK Rev.02 

Addressable Volumetric PIR Motion Detector 

 

OPERATING AND INSTALLATION MANUAL 

 

GENERAL 

S2000-IK  Revision  02  Addressable  Volumetric  Passive  Infrared  (PIR)  Motion  Detector  (hereinafter  referred  to  as  the 
detector)  is  designed  to  detect  intrusion  into  the  protected  premises  with  sending  alarms  to  the  connected  polling  loop 
controller S2000-KDL or S2000-KDL-2I via its two-wire multiplex addressable polling loop (PL). 

The detector is intended to operate as a part of an Orion fire and intrusion alarm system. 

The detector features volumetric detection zone providing pet immunity for animals up to 20 kg. 

The detector is immune against lighting and radio frequency interference. 

KEY FEATURES 

  Dual-element pyro-electric infrared sensor 

  High-density coverage offering high probability of detecting an intruder 

  Protected against insects entering to the pyro-electric infrared sensors 

  Sabotage-resistant zones just beneath the detector prevents unauthorized access to the detector 

  Digital signal processing 

  Powered via the multiplex addressable polling loop of a PL controller 

  Supports DPLS_v2.51 protocol 

SPECIFICATIONS 

Detection Zone 

Volumetric (see Figure 1) 

Detection Range 

10 m 

Input Voltage 

From the PL controller 

Consumed Current 

0.5 mA max w/o indication 

Horizontal Field-of-View 

90

°

 

Operating Temperatures 

30 to +50°C 

Relative Humidity 

95% at 25°C, non-condensing 

Ingress Protection Rating 

IP41 

Overall Dimensions (H x W x D) 

105 mm 

×

 75 mm 

×

 56 mm  max 

Weight 

0.1 kg max 

Mounting Height 

2.3 meters 

MOUNTING LOCATION CONSIDERATIONS 

The  detector  is  intended  to  be  used  indoors.  Considering  a 
location  to  mount  the  detector,  please  take  into  account  that  the 
detection  zone  must  not  be  obscured  by  any  non-transparent 
objects  such  as  curtains,  houseplants,  cabinets,  room  dividers, 
etc. as well as by glass or mesh partitions. 

Do not locate the detector where it can be exposed to false alarm 
sources such as windows, air conditioners, heaters, radiators, etc. 

Wires of the multiplex addressable polling loop should be located 
away from high-voltage electric cables. 

The  detector  allows  wall  or  corner  mounting  at  a  height  of  2.3 m 
above  the  floor.  This  provides  the  detection  range  at  least  10 
meters. The detection pattern is shown in Figure 1. 

 

 

Figure 1: S2000-IK Rev.02 Detection Pattern

 