background image

 

4

1

 

Figure 1.

 Top View

 

165

2

1

1

90

90

1

2

0

4

4

 

Figure 2.

 Overall and Mounting Dimensions

 

WARNING! 
While  connecting  mains  power  wires  220 V  to  the  input  terminal  block,  please 

observe  correct  polarity  of  connecting  the  Line  and  Neutral  circuits.  Connect  the 
circuits to the RIP as shown in Figure 3. 

S

witch

Uo

u

t

S

witch

Ub

a

t

S

wit

ch

Um

a

in

s

 

Figure 3.

 RIP-12 mod.14 (RIP-12-2/7P2-R) Connection Diagram 

2.2.5

 

Following are the recommended cross section areas of the wires to be connected to 

the RIP: 

1)

 

To connect the RIP to mains power 220 V (the XT3 terminal block): 0.75…2.5 mm

2

 

for stranded wires or 1…2 mm in diameter for solid wires; 

2)

 

To connect the load: 0.5…2.5 mm

2

 for stranded wires or 0.8…2 mm in diameter for 

solid  wires  taking  into  account  the  maximum  voltage  drop  on  wires  at  maximum  load 
current (the minimum allowable voltage at the load). 

2.2.6

 

If  several  load  circuits  are  to  be  connected,  it  is  recommended  to  use  Bolid 

manufactured BZK rev.01 power distribution module. 

2.2.7

 

The tamper switch of the RIP can be used to mute the buzzer. 

2. Press on the notches and open the cover 

Summary of Contents for RIP-12

Page 1: ...t missed battery shutting the battery off in case of its discharge as well as indication of possible RIP faults during operation see Table 2 1 1 6 The RIP provides limiting of the battery charger voltage and current depending on the temperature within the device enclosure 1 1 7 The RIP provides monitoring battery conditions and its connecting circuit by comparing with maximum admissible internal r...

Page 2: ...messages closed open state of the circuits is at least 3 s The time of delay for messages sent by the relays К1 К3 is 3 s The time of delay for messages Battery Low sent by the K2 relay does not exceed 1 min States of the solid state relay circuits are shown in Table 1 Table 1 Circuit Purpose Contact State К1 Output voltage monitoring In case of normal output voltage1 the contact is closed In case...

Page 3: ...7 Package 1 pc no battery is included into the delivery 2 OPERATING INSTRUCTIONS 2 1 Safety Precautions 2 1 1 The current carrying circuits connected with mains power 220 V are a source of potential hazard These circuits are covered by a protective housing on the RIP printed circuit board 2 1 2 The safety precautions are as follows 1 The fuse shall always be good and its rating shall be as stated ...

Page 4: ...n areas of the wires to be connected to the RIP 1 To connect the RIP to mains power 220 V the XT3 terminal block 0 75 2 5 mm2 for stranded wires or 1 2 mm in diameter for solid wires 2 To connect the load 0 5 2 5 mm2 for stranded wires or 0 8 2 mm in diameter for solid wires taking into account the maximum voltage drop on wires at maximum load current the minimum allowable voltage at the load 2 2 ...

Page 5: ...nutes Operability of the battery charger at least once per 15 minutes Presence of mains voltage No overload and no short circuit conditions at the output 2 4 3 If no mains power is applied then the load starts to be powered by the battery the buzzer periodically emitting low battery warning beeps the POWER LED being off and the BAT LED and 12 V LED illuminating 2 4 4 If the battery voltage has dro...

Page 6: ...2 Current Conditions of the RIP Indicators Buzzer POWER BAT 12 V TROUBLE green green green amber 1 Mains utility power is starting up no battery is connected ON 0 4 s 8 times 2 Mains power is OK the battery is nor charged OFF 3 s 3 Mains power is OK the battery is charged 4 DC output overcurrent The battery is available ON 15 60 s 2 Hz ON 1 5 s 2 times 5 Mains power is off the battery voltage exce...

Page 7: ...aking into account the technical guide Maintenance of fire alarm systems and public address and general alarm systems of Types 1 2 in Orion ISS developed by the NVP Bolid Company 4 TROUBLESHOOTING N o Symptom Cause Action 1 The RIP fails to be turned on the mains power is on 1 Blown fuse F1 2 Faulty wiring 3 Long duration overload at the RIP DC output 1 Check the mains power voltage at the ХТ3 ter...

Page 8: ...13 В 00703 6 2 RIP 12 mod 14 RIP 12 2 7P2 R Battery Backed Power Supply meets the requirements of Technical Regulations of Custom Union TR CU 004 2011 TR CU 020 2011 and is covered by Conformity Declaration ЕАЭС RU Д RU МЛ66 В 02301 6 3 RIP 12 mod 14 RIP 12 2 7P2 R is covered by the certificates of conformity of transport safety technical arrangements with their functional properties No МВД РФ 03 ...