The  insulating  strength  of  the  live  parts  of  the  RIP  is  at  least  1500 V  (50 Hz) 

between circuits connected to mains 220 V and any circuits not connected with the mains. 

1.2.19

 

The  electrical  insulation  resistance  between  circuits  mentioned  above  is  at  least 

20 mega ohms (in normal conditions as per with GOST 12997-84). 

1.2.20

 

The average service life of the RIP is at least 10 years provided that the battery is 

to be replaced at least once per 5 years. 

1.2.21

 

The design of the RIP provides its fire safety in case of emergency operation and 

upon the breach of operational regulations in accordance with GOST 12.1.004-91. 

1.2.22

 

Enclosure protection degree: IP30 as per GOST 14254-96. 

1.2.23

 

The overall dimensions of the RIP are 165

×

211

×

90 mm max. 

1.2.24

 

The weight of the RIP with the battery doesn’t exceed 3.5 kg. 

1.2.25

 

As  to  the  content  of  precious  materials  the  product  does  not  require  accounting 

for storage, writing-off, and/or disposal. 

1.2.26

 

The content of non-ferrous metals: does not require accountability for retirement 

and further disposal. 

1.3

 

Standard Delivery 

1)

 

Battery Backed Power Supply* 

– 1 pc. 

2)

 

Instruction Manual 

– 1 pc. 

3)

 

Fuse (2 A) 

– 1 pc. 

4)

 

Woodscrew 1-4

х

30.20.019 GOST 1144-80  – 4 pcs. 

5)

 

Wall Plug 8

х

30S 

– 4 pcs. 

6)

 

Cable Grommet GM-3 

– 2 pcs. 

7)

 

Package 

– 1 pc. 

*

no battery is included into the delivery

 

2

 

OPERATING INSTRUCTIONS 

2.1

 

Safety Precautions 

2.1.1

 

The  current  carrying  circuits  connected  with  mains  power  220 V  are  a  source  of 

potential  hazard.  These  circuits  are  covered  by  a  protective  housing  on  the  RIP  printed 
circuit board. 

2.1.2

 

The safety precautions are as follows: 

1)

 

The  fuse  shall  always  be  good  and  its  rating  shall  be  as  stated  in  the  operation 
documentation; 

2)

 

Do always shut off mains utility power before opening the RIP; 

3)

 

Do NOT remove the protective housing from the PCB. 

2.1.3

 

Do always shut off mains utility power before mounting, wiring, and maintaining 

the RIP. 

2.1.4

 

Only qualified staff certified with the third or higher safety qualification level can 

mount and maintain the RIP. 

2.2

 

Mounting and Preparing for Use 

2.2.1

 

The RIP is to be installed on a wall or another structure of the protected premises 

at  places  protected  against  exposure  to  atmospheric  precipitation,  mechanical  damage,  and 
unauthorized access. 

2.2.2

 

To open the RIP enclosure, do the following: 

1)

 

Unscrew the bolt fastening the front cover on the top side of the RIP enclosure; 

2)

 

Press  on  the  notches  on  the  top  side  of  the  RIP  enclosure  and  open  the  cover 
(Figure 1). 

2.2.3

 

Prior  to  attaching  the  RIP  to  a  surface  and  connecting  it  to  power  wires,  install  the 

GM -3 grommets provided into the enclosure holes. 

2.2.4

 

Fasten  the  RIP  at  the  selected  place.  The  overall  and  mounting  dimensions  are 

shown in Figure 2. 

Summary of Contents for RIP-12

Page 1: ...t missed battery shutting the battery off in case of its discharge as well as indication of possible RIP faults during operation see Table 2 1 1 6 The RIP provides limiting of the battery charger voltage and current depending on the temperature within the device enclosure 1 1 7 The RIP provides monitoring battery conditions and its connecting circuit by comparing with maximum admissible internal r...

Page 2: ...messages closed open state of the circuits is at least 3 s The time of delay for messages sent by the relays К1 К3 is 3 s The time of delay for messages Battery Low sent by the K2 relay does not exceed 1 min States of the solid state relay circuits are shown in Table 1 Table 1 Circuit Purpose Contact State К1 Output voltage monitoring In case of normal output voltage1 the contact is closed In case...

Page 3: ...7 Package 1 pc no battery is included into the delivery 2 OPERATING INSTRUCTIONS 2 1 Safety Precautions 2 1 1 The current carrying circuits connected with mains power 220 V are a source of potential hazard These circuits are covered by a protective housing on the RIP printed circuit board 2 1 2 The safety precautions are as follows 1 The fuse shall always be good and its rating shall be as stated ...

Page 4: ...n areas of the wires to be connected to the RIP 1 To connect the RIP to mains power 220 V the XT3 terminal block 0 75 2 5 mm2 for stranded wires or 1 2 mm in diameter for solid wires 2 To connect the load 0 5 2 5 mm2 for stranded wires or 0 8 2 mm in diameter for solid wires taking into account the maximum voltage drop on wires at maximum load current the minimum allowable voltage at the load 2 2 ...

Page 5: ...nutes Operability of the battery charger at least once per 15 minutes Presence of mains voltage No overload and no short circuit conditions at the output 2 4 3 If no mains power is applied then the load starts to be powered by the battery the buzzer periodically emitting low battery warning beeps the POWER LED being off and the BAT LED and 12 V LED illuminating 2 4 4 If the battery voltage has dro...

Page 6: ...2 Current Conditions of the RIP Indicators Buzzer POWER BAT 12 V TROUBLE green green green amber 1 Mains utility power is starting up no battery is connected ON 0 4 s 8 times 2 Mains power is OK the battery is nor charged OFF 3 s 3 Mains power is OK the battery is charged 4 DC output overcurrent The battery is available ON 15 60 s 2 Hz ON 1 5 s 2 times 5 Mains power is off the battery voltage exce...

Page 7: ...aking into account the technical guide Maintenance of fire alarm systems and public address and general alarm systems of Types 1 2 in Orion ISS developed by the NVP Bolid Company 4 TROUBLESHOOTING N o Symptom Cause Action 1 The RIP fails to be turned on the mains power is on 1 Blown fuse F1 2 Faulty wiring 3 Long duration overload at the RIP DC output 1 Check the mains power voltage at the ХТ3 ter...

Page 8: ...13 В 00703 6 2 RIP 12 mod 14 RIP 12 2 7P2 R Battery Backed Power Supply meets the requirements of Technical Regulations of Custom Union TR CU 004 2011 TR CU 020 2011 and is covered by Conformity Declaration ЕАЭС RU Д RU МЛ66 В 02301 6 3 RIP 12 mod 14 RIP 12 2 7P2 R is covered by the certificates of conformity of transport safety technical arrangements with their functional properties No МВД РФ 03 ...

Reviews: