7 Troubleshooting
Yes
No
No
No
Yes
Yes
No
FAULT
CAUSE
REMEDY
Cooling air outlet too
high / High dew point
Overload protector
(SK/HT) tripped
Compressor noisy
Excessive
current
consumption
High pressure drop on
air side
High refrigerant
discharge
pressure
Condenser dirty
Ambient
temperature over
122°F (50°C)
Compressor
components
perished
Condenser dirty
Heat exchanger fouled
with debris
Fan pressure switch (PV)
calibration
error or
damaged
Clean
condenser
Reduce
temperature
Repair or
replace
compressor
Clean
condenser
Replace
pressure switch
Seek external as-
sistance
Ice formation on evapo-
rator (low evaporation
pressure)
By-pass air fl ow keep-
ing air inlet open. Open
condensate drain valve
manually.
Restart appliance checking
setting of expansion
valve.
Condenser
dirty
Fan does
not work
Replace
fan
Clean
condenser
Clean heat ex-
changer (blow com-
pressed air in opposite
direction to operating
air fl ow). Fit/renew
prefi lter
Fan does
not work
Compressor
winding insulation
partially perished
(compressor
too hot)
Repair
fan
Fan does not work
Excessive
thermal load (compressor
head too hot)
Reduce
compressed air
quantity or air
temperature
Repair
fan
Insuffi
cient
refrigerant: repair any
leaks and recharge the
circuit
Low current
consumption
Yes
No
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Summary of Contents for BS125-175
Page 2: ......
Page 19: ... Appendix 1 BS125 175 Appendice Anhang Appendix Anexo ...
Page 25: ... 8 6 Dimensional drawing 7 BS125 175 i n c h e s mm ...
Page 26: ... 8 7 Refrigerant circuit 8 BS125 175 BS125 BS150 175 ...
Page 27: ... 8 8 Wiring diagram BS125 9 BS125 175 230 Vac ...
Page 28: ... 8 8 Wiring diagram BS150 10 BS125 175 230 Vac ...
Page 29: ... Wiring diagram BS175 11 BS125 175 ...
Page 30: ......
Page 31: ......