background image

If draft of –0.02" WC cannot be produced with an existing vent system, a draft inducer may be
required. Installations common vented with large vent hood equipped appliances such as
heating boilers may require vent dampers on the heating boiler connectors for proper vent
operation during summer months.

Check the building for items that can cause severe negative pressure problems such as large
exhaust fans. If these devices are installed in the same building check for their effect on draft
and combustion. All fuel burning appliances must be isolated from the effects of these devices
to operate properly. Failure to address this issue will result in unsafe operation and shorten
appliance life spans.

Your Bock Water Heater may also be operated with a power venter. The power venter must be
properly sized and adjusted to provide proper draft. Power venter wiring must turn on the
power venter on a call for heat and must prove venter operation before allowing the burner to
start. Refer to the power venter instructions for proper wiring and adjustment procedures.

CONNECT WATER PIPING

Connect cold inlet and hot outlet to fittings on top of water heater except models 33PG and
40PG. These models have cold water inlets located on the side of the tank. See drawing and
note below. Be careful not to apply any heat to the water heater nipples. Install dielectric
unions and shut off valves on both hot and cold water lines. Models 72PG through 541PG
have larger fittings located on the side of the tank or under the drain valve for use
as recirculation/return connections. Larger return fittings are optional on smaller models.
Alternatively recirculation/return lines can be plumbed to the cold water inlet.

33PG and 40PG models are equipped with a brass inlet
bushing installed in the tank. Heaters equipped with this
bushing are marked next to the inlet by the decal shown
on the left. The purpose of this bushing is to help keep the
tank bottom free of sediment by aiding tank flushing.
This bushing must be located as shown on the decal to
function properly. Do not allow the bushing to rotate out
of position when tightening the inlet fittings.

An approved pressure and temperature relief valve is factory installed in the opening provided
in the upper right-hand side of the water heater. Pipe the T&P valve outlet to within 6" of the
floor or to a floor drain with a free flowing drain pipe.

CAUTION: Scalding injury and/or water damage can occur from either the manual lifting

of the lever or the normal operation of the T&P valve if it is not piped to a proper drain.

If the valve fails to flow water or reseat, call your plumber.

Check incoming water line for backflow preventers or water pressure reducing valves, as these
may cause pressure to build up in the water heater and result in tank failure. If this water
heater is installed in a closed system or if backflow preventers and pressure regulators are
installed, a properly sized expansion tank must be installed.

Note:

Do not try to heat hard water as this will drastically reduce heater life. Install a water

softener or other scale reducing water treatment system if the water heater is being installed in
a hard water area (water hardness higher than seven grains).

BURNER AND AQUASTAT INSTALLATION

Remove the cardboard core from the burner opening in the water heater. Inspect the burner
opening in the water heater and verify that the chamber is aligned with the burner opening
and has not shifted in shipment. Also verify that the chamber and insulation has not been
damaged in shipment. Some burner models are equipped with adjustable mounting flanges.
When installing these burner models measure the distance from the inside bottom edge of the
combustion chamber to the burner mounting bracket on the water heater jacket. Subtract

1

8

"

from this measurement and locate the burner mounting flange that distance from the end of

Page 6

Power Gas

Summary of Contents for 50 ESPG

Page 1: ...water temperature is needed in part of the water system automatic temperature limiting devices must be used on all lines to water taps WARNING Flammable vapors may be drawn to this water heater from...

Page 2: ...N A 171 4 120 60 270 40 PG 40 126 1 2 3 4 3 4 1 90 134 61 20 6 54 18 120 60 295 50 ESPG 50 140 1 2 1 11 2 11 2 90 142 52 26 6 131 2 181 2 120 60 345 51 PG 50 152 1 2 1 1 3 4 90 159 59 24 6 11 18 120 6...

Page 3: ...separate units The aquastat and immersion well are packed with the burner If damage is observed or parts appear to be missing contact your wholesaler A burner installation and setup manual is also pac...

Page 4: ...upply will result in poor burner water heater performance and nuisance lock outs Unsafe levels of carbon monoxide CO conden sation and sooting may result if the room does not have an adequate air supp...

Page 5: ...et Shorter vent heights could result in unstable draft and nuisance lock outs The venting system should be sized according to National Fuel Gas Code NFPA 54 ANSI Z223 1 most recent edition using the F...

Page 6: ...by the decal shown on the left The purpose of this bushing is to help keep the tank bottom free of sediment by aiding tank flushing This bushing must be located as shown on the decal to function prop...

Page 7: ...test Edition For LP installations refer to NFPA 58 latest edition for proper gas piping Supply piping should be sized according to the charts found in the National Fuel Gas Code for natural gas applic...

Page 8: ...pm 0 preferred O2 should be between 3 and 6 3 5 is preferred for Carlin and Midco burners see burner manual for more detail Note Your Bock Power Gas Water Heater system may produce 80 to 120 ppm CO an...

Page 9: ...se accumulations can be controlled to an extent by softening the water or using other water treatment systems The tank should be inspected every six months Drain remove the hand hole cover and make a...

Page 10: ...ration at 110 S Dickinson Street Madison Wisconsin 53703 Company warrants to the owner the tank of this water heater will not leak due to defective materials or workmanship for FIVE 5 years from the d...

Page 11: ...removal of the magnesium anode rods noise odor rusty water the installation of an insulation blanket installation outside of the United States excluding Canada or on which the serial numbers have bee...

Page 12: ...64 3 5 WC 7 3 5 WC 71PG 173 000 EC200 9 NONE 3 5 WC 3 3 5 WC 190PG 190 000 EC300 3 5 5 16 3 5 WC 2 3 5 WC 72PG 199 000 EC300 4 5 P 3 5 WC 1 3 5 WC 73PG 242 000 EC300 5 W 3 5 WC G 3 5 WC 241PG 277 000...

Reviews: