WHEN YOU RECEIVE YOUR NEW STORAGE TANK

Check the new equipment to see if all components are in good condition. The T&P valves,
aquastat and immersion well are supplied by the installer.

TEMPERATURE CONTROLS

Bock storage tanks are equipped with 

3

4

'' tappings for the installation of immersion

temperature controls. Any temperature control approved for use in hot water systems is
acceptable. Bock recommends the use of a control with an adjustable differential so that the
differential can be adjusted to match that of your heat source controls. Setting the storage
tank temperature control 5

°

lower than the water heater temperature control is also

recommended. This is to ensure that when the storage tank calls for heat and the circulator is
turned on, the water being circulated is cool enough to cause the water heater to start. If the
burner does not start then the circulator could run for long periods of time, wasting energy.

Note:

The recommended water temperature for domestic use is 120

°

. Higher water

temperatures can result in scalding. If higher or lower water temperatures are needed, point
of use tempering devices are recommended.

T&P VALVES

Temperature and pressure relief valves must be installed on all storage tanks by the installer.
All Bock storage tanks are also equipped with 

3

4

'' or 1'' tappings for the installation of

properly sized temperature and pressure relief valves. These are located on the side near the
top of vertical tanks and on the top surface of horizontal storage tanks. Relief valves are rated
for maximum system pressure and temperature as well as Btu input of the heating appliance.
This information is normally supplied on a metal tag attached to the end of the valve. For a
normal domestic water system maximum system pressure is 150 psi and temperature limit is
210

°F

. The Btu per hour rating will be listed next to the AGA or CSA logo on the tag under

the temperature and pressure data. Be certain to use a relief valve that is rated for the Btu per
hour input of the heating appliance. For example, if you are connecting a storage tank to a
water heater with a 50,000 Btu per hour input then the relief valve installed in the storage
tank must be rated for a minimum of 50,000 Btu per hour. 

PIPING

Bock storage tanks are equipped with many different fitting sizes and configurations
depending on intended use. However, all storage tanks will have some common features. All
Bock storage tanks will have two or more anode rods installed through the top of the storage
tank. Bock storage tanks typically have three large tappings, normally 2 inches NPT or larger,
in the side of the tank. The exact location of these fittings will vary depending on tank
model and any special options ordered. The tapping nearest the bottom of the tank is used 
as a cold water inlet and/or a connection to return water from the storage tank to the heat
source. A second tapping of similar size located higher up the side of the tank is used to
return heated water from the heat source. A hot water outlet is located on the top of the tank.

Summary of Contents for 119ST

Page 1: ... must be installed in accordance with all local codes and ordinances HANDLING Before uncrating check for shipping damage Report any damage to your carrier Note damage on bill of lading or delivery receipt and file a claim LOCATION This storage tank should be located in a central location to the piping system as close as possible to the heat source and in an area not subject to freezing temperature...

Page 2: ...2 28 54 22 7 385 A C W e i g h t l b s D i m e n s i o n s Figure 2 80ST 119ST B Drain Valve Supply Return Conn Aquastat Conn Supply Return Conn T P Relief Valve Conn C A D E D r a i n V a l v e 30 R e l i e f V a l v e 45 Aquastat 0 ANODE ANODE 45 S u p p l y R e t u r n Hot Outlet Figure 1 30ST 50ST C A Supply Return Conn Drain Valve Supply Return Conn Aquastat Conn D E B T P Relief Valve Conn 3...

Page 3: ...on w External Jacket Storage gal Working Pressure Overall Diameter T P Relief Valve Conn Inlet Return Conn Hot Outlet Conn Aquastat Conn Overall Height Length Shipping Weight lbs 119ST A 150 Standard 119 150 28 1 x 1 NPT 2 2 65 385 200ST A 125 Standard 200 125 34 2 x 1 NPT 2 2 79 872 200ST A 150 Standard 200 150 34 2 x 1 NPT 2 2 79 872 Table 2 ASME ST Dimensions Figure 3 ASME Vertical ...

Page 4: ...side near the top of vertical tanks and on the top surface of horizontal storage tanks Relief valves are rated for maximum system pressure and temperature as well as Btu input of the heating appliance This information is normally supplied on a metal tag attached to the end of the valve For a normal domestic water system maximum system pressure is 150 psi and temperature limit is 210 F The Btu per ...

Page 5: ...heat source to the large fitting nearer the center of the storage tank or the large fitting near the top of the side DRAWING 1 Drawing 1 shows a typical installation for a home or business with high peak loads such as multiple showers in the morning This drawing also shows an optional bypass system N C Valve to allow the storage tank to be isolated from the system Cold water is connected to the in...

Page 6: ...he hot water outlet of the water heater to draw hot water back into the storage tank In times of low hot water use this pump can be turned off by a switch or timer preventing the storage tank from being heated A check valve is also used as in the other systems to prevent cold water from diluting the hot water stream DRAWING 3 Drawing 3 shows a storage tank connected to a boiler This system is esse...

Page 7: ...urned to the second water heater in the series DRAWING 5 Drawing 5 shows a Bock storage tank piped to a water water geothermal heat pump supplying heated water to a radiant floor system drawing courtesy of Enertech Mfg MAINTENANCE All Bock storage tanks are equipped with magnesium anode rods These rods must be checked annually and replaced when they become worn to 3 8 inch diameter or less to ensu...

Page 8: ...ded it will remain warranted under this section as if it were the original tank For example if we send you a replacement tank under this limited warranty two years after the original installation date then the replacement tank will remain warranted for the remaining three years after the original installation date HOW DO YOU GET SERVICE UNDER THE LIMITED WARRANTY In order for the warranty period t...

Page 9: ...w the care and maintenance instructions provided with the storage tank Remove the anode rods Fail to inspect and replace the anode rods you must retain and present your paid receipts as proof of anode rod replacement HOW DOES STATE LAW RELATE TO THIS LIMITED WARRANTY This is a limited warranty WE MAKE NO OTHER EXPRESS WARRANTIES WITH RESPECT TO THIS WATER HEATER We will not assume nor authorize an...

Page 10: ...Page 10 Storage Tanks NOTES ...

Page 11: ...Storage Tanks Page 11 NOTES ...

Page 12: ...Storage Tanks 23950 ...

Reviews: