3. MOUNTING THE HEATER 

 

IMPORTANT!

 Ensure that the mounting surface / ceiling supports are capable of 

taking the additional weight of the heater.  

 

IMPORTANT!

  Before  cutting  out  the  hole  to  take  the  heater  ensure  there  is 

200mm clearance behind and that there are no cables or pipes in the way.

 

The  heater  is  intended  for  installation  in  ceilings,  walls  or  bulkheads.  When  wall 
mounted the heater MUST be positioned horizontally. For optimum results do not fit in 
ceilings lower than 1.8m or higher than 3m. As air is only introduced through the front of 
the unit the heater may be sited anywhere. The air intake and discharge areas must be 
kept  completely  clear  for  a  minimum  of  1.5m  from  the  front  of  the  heater.  In  an  area 
using multiple units, heaters should be spread to provide an even heat distribution.  

Cut a rectangular hole 560mm long x 150mm wide (See drawing to the right).  

The  heater  should  be  held  in  position  using  suitable  fixtures  using  the  pre-punched 
slots / holes in the face of the unit. 

4.  ELECTRICAL CONNECTIONS 

4.1  230V SINGLE PHASE 

– Without controls. 

Please make sure you have read the Safety instructions and that you are a suitably qualified electrician before continuing. 
Drawings show connections inside the black terminal box on the outside of the heater. 

Do NOT use power tools to undo or do up terminal screws.

 

Please Note:- Specified cable sizes are for typical installations, correction factors may need to be used when determining actual cable sizes. 
 

 
Standard Connection and Use 
 
Use 1.5mm² 3 Core Mains Cable (see note above). 
Connect Brown wire 

– Terminal 1 or L. 

Connect Blue wire 

– Terminal 5 or N. 

Connect Green / Yellow wire 

– Terminal E or 

 
Ensure the 3 links 

are in position between terminals 1 and 2, 2 and 3, 3 and 4 

as shown in drawing to the left. 
 
 
 
If  you  wish  to  de-rate  the  heater  from  3kW  to  2kW  remove  the  link 

between 

terminal 3 and terminal 4. Ensure you tighten up the screws after  removing the link. See 
drawing to the right. 
 
 
 

 
 

PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE

 

 

4.2  230V SINGLE PHASE 

– With Thermostat (RST-TP). 

Please make sure you have read the Safety instructions and that you are a suitably qualified electrician before continuing. 
Drawings show connections inside the black terminal box on the outside of the heater and the inside of the RST-TP Thermostat. Other thermostats 
may be used BUT they must be suitable for a 3kW load. 

Do NOT use power tools to undo or do up terminal screws.

 

Please Note:- Specified cable sizes are for typical installations, correction factors may need to be used when determining actual cable sizes. 

 

Standard Connection using RST-TP Thermostat 

 

Use 1.5mm² 3 Core Mains Cable (see note above) 
Use  1.5mm²  4  Core  Cable  to  connect  the  heater  to  the 
thermostat (see note above). 
 
Remove  link 

in  heater  terminal  box  between 

terminals 1 and 2. 
Ensure  the  remaining  2  links  are  in  position  between 
terminals 2 and 3, 3 and 4 as shown in drawing to the left. 
 
Mains Cable 
Connect Brown wire 

– Terminal 1 or L. 

Connect Blue wire 

– Terminal 5 or N. 

Connect Green / Yellow wire 

– Terminal E or  

 
Heater to Thermostat Cable 

– (Colours for reference only) 

Connect  Brown  wire 

–  Terminal  1  or  L  of  heater  and 

Terminal 3 of Thermostat.  
Connect Grey wire 

– Terminal 2 of heater and Terminal 1 

of Thermostat. 
Connect  Blue  wire 

–  Terminal  5  or  N  of  heater  and 

Terminal 4 or N of   Thermostat. 

Connect  Green  /  Yellow  wire 

–  Terminal  E  or 

of  the 

heater and earth connection on Thermostat. 

 

 
If  you  wish  to  de-rate  the  heater  from  3kW  to  2kW  remove  the  link 

between  terminal  3  and  terminal  4.  Ensure  you  tighten  up  the 

screws after removing the link.  
 

PLEASE CHECK ALL CONNECTIONS BEFORE TURNING ON AS INCORRECT WIRING IS NOT COVERED BY THE GUARANTEE

 

 