background image

Development and production of systems for measurement and control

 5.1. Screens structure

Meaning   of   each   screen   is   easily   identified   by   usage   of   standard   ISO   symbols   and   value   parameters.   Every
displayed parameter value is shown with its variable.

Phase voltage

Phase to phase voltage

Voltage THD

3

rd

 voltage harmonics

19

th

 voltage harmonics

..

..

Phase current

Current in neutral

Current THD

3

rd

 current harmonics

19

th

 current harmonics

..

..

System frequency

Cos φ

Power factor

BMR 

trading

Horní lán 17
779 00 Olomouc

Czech Republic

7

Tel: +420 778 066 566

[email protected]

www.bmr-trading.com

Summary of Contents for PLA34

Page 1: ...PLA 34 Power quality analyzer class S User and service manual version 1 0 BMR trading Horní lán 17 779 00 Olomouc Czech Republic 1 Tel 420 778 066 566 export bmr trading com www bmr trading com ...

Page 2: ...s 9 7 1 Menu P1 9 7 2 Menu P2 9 7 3 Advanced setting from PMS software 9 7 3 1 Main parameters 10 7 3 2 LAN settings 12 7 3 3 NTP server Time zone 13 7 3 4 Transient 14 7 3 5 Event 15 7 3 5 1 RVC Ripple control 16 7 3 6 Inputs Outputs 16 7 3 6 1 Alarms 17 7 3 6 2 Display settings 18 7 3 6 3 Data storage 18 7 3 7 Memory settings 19 7 3 8 About 20 7 4 Connection of PLA34 to LAN with NAT server 21 8 ...

Page 3: ... and parameters cursor key for moving up in menu and parameter change to higher value cursor key for moving down in menu and parameter change to lower value ESC key for canceling or return Picture 2 Rear panel description BMR trading Horní lán 17 779 00 Olomouc Czech Republic 3 Tel 420 778 066 566 export bmr trading com www bmr trading com ...

Page 4: ... I 0 999 0 999 Class 1 Group of harmonics I 0 999 0 999 Class 1 Actual flicker hidden 0 4 10 0 Pist 0 4 10 0 Pist Class A Short term flicker 0 4 10 0 Pst 0 4 10 0 Pst Class A Long term flicker 0 4 10 0 Plt 0 4 10 0 Plt Class A Under voltage 0 100 0 100 0 2 Over voltage 0 100 0 100 0 2 Unbalance U 0 100 0 100 0 15 Neutral point displacement 10 600 V 0 1 MV 0 2 K factor Unbalance I 0 5 Transients 25...

Page 5: ...tails on the label The connection cables for the supply voltage has to be connected using a fuse Use a fuse 6 A type C 4 2 Measuring inputs Voltage measuring inputs have to be connected via circuit breaker or switch and fuse 10 A which are placed close to the device Current measuring inputs have to be connected via current transformers either 5A or 1A ratio Picture 3 Full device connection at TN C...

Page 6: ...ndingly If the network configuration is not known the Ethernet cable should not be plugged into the device 4 5 USB Device has one USB interface of type B 4 6 Digital inputs outputs PLA34 has built in two digital inputs outputs which are related to several functions of device Picture 4 input output connection 5 Operation PLA34 allows simple operation of basic screens with most interesting parameter...

Page 7: ... displayed parameter value is shown with its variable Phase voltage Phase to phase voltage Voltage THD 3rd voltage harmonics 19th voltage harmonics Phase current Current in neutral Current THD 3rd current harmonics 19th current harmonics System frequency Cos φ Power factor BMR trading Horní lán 17 779 00 Olomouc Czech Republic 7 Tel 420 778 066 566 export bmr trading com www bmr trading com ...

Page 8: ...ee phase power Active energy consumption Reactive L energy consumption Reactive C energy consumption Active energy supply Reactive L energy supply Reactive C energy supply 5 1 1 Flicker Device calculates flicker according to the norm EN61000 4 15 It provides values for short term flicker 10 minutes long term flicker 2 hours 6 Web server BMR trading Horní lán 17 779 00 Olomouc Czech Republic 8 Tel ...

Page 9: ...lendar settings Y year M month d day H M Internal clock setting H hours M minutes PAS Instrument password settings 0001 9999 rES Device configuration reset to the factory settings 7 2 Menu P2 Settings related to the device itself such as display parameters colors time password protection and reset of all settings Parameter Description Factory settings Settings range IP PLA34 IP address in the loca...

Page 10: ...f the nominal voltage and frequency for flicker calculation 230V 50Hz 120 230V 50 60Hz Voltage transformer ratio Enable the usage of measuring voltage transformer No No Yes Primary voltage 230V 1 750 kV Secondary voltage 230V 1 750 kV Current transformer ratio No No Yes Primary current 1A 1 750 kA Secondary current 1A 1 5 A Type of averaging Type of averaging method Static Static Sliding Averaging...

Page 11: ...Development and production of systems for measurement and control BMR trading Horní lán 17 779 00 Olomouc Czech Republic 11 Tel 420 778 066 566 export bmr trading com www bmr trading com ...

Page 12: ...8 001 001 MAC Web server settings advance menu WEB server Activates the internal web server of PLA34 User name Webserver user name admin Password Webserver password 1234 Web port Port of web server 80 FTP server Activates the internal FTP server of PLA34 User name FTP server user name admin Password FTP server password 1234 FTP port Port of FTP server 21 Modbus TCP Activates the Modbus TCP communi...

Page 13: ...bove the manual clock settings Clock synchronization by NTP is fully automatic and there is no need to set anything The selection of closest NTP server is adjustable in software PMS For the finding the closest NTP server refer to the following link http support ntp org bin view Servers StratumOneTimeServers BMR trading Horní lán 17 779 00 Olomouc Czech Republic 13 Tel 420 778 066 566 export bmr tr...

Page 14: ...setting 20 1 100 Increase time Time delay before next transient recording after transient start 5s 1 20 s Increase value Increment value for transient insensitivity after recording start 10V 1 750000 V Post samples Number of recorded samples after the transient start 768 0 8000 Pre samples Number of recorded samples before the transient start 768 0 8000 Memory for capturing the transients amplitud...

Page 15: ...esis 5 1 20 Interruption Threshold 5 1 100 Hysteresis 2 1 20 Over current Threshold 110 100 500 Hysteresis 5 1 20 Pre Samples Number of recorded half periods Urms1 2 10ms 1 before event 10 0 4000 Post Samples Number of recorded half periods Urms1 2 10ms 1 after event 150 0 4000 Memory for capturing the samples of RMS curve is fixed on the maximum of 4000 samples Definition of number Pre and Post s...

Page 16: ...y control industrial equipment revenue meters and other devices Parameter Description Factory setting Setting range RVC threshold The RVC threshold is a percentage of Udin 3 3 1 100 RVC hysteresis The RVC hysteresis is a smaller percentage of Udin 1 1 20 Ripple control Adjustable by PMS 50 Hz 50 Hz 3 kHz According to the norm the ideal settings is RVC threshold on 3 5 of Udin and hysteresis on 1 o...

Page 17: ...Development and production of systems for measurement and control 7 3 6 1 Alarms BMR trading Horní lán 17 779 00 Olomouc Czech Republic 17 Tel 420 778 066 566 export bmr trading com www bmr trading com ...

Page 18: ...on which the Modbus TCP is accessible 80 7 3 6 3 Data storage Measured parameters can be recorded in the internal flash memory For this purposes setup cart Data storage offers the list of all parameters that can be stored PLA34 allows to define 5 different time intervals with adjustable time and recorded parameters BMR trading Horní lán 17 779 00 Olomouc Czech Republic 18 Tel 420 778 066 566 expor...

Page 19: ...for measurement and control 7 3 7 Memory settings Settings related to RS485 interface with Modbus RTU protocol support BMR trading Horní lán 17 779 00 Olomouc Czech Republic 19 Tel 420 778 066 566 export bmr trading com www bmr trading com ...

Page 20: ...of systems for measurement and control 7 3 8 About Information about the vendor and device firmware version BMR trading Horní lán 17 779 00 Olomouc Czech Republic 20 Tel 420 778 066 566 export bmr trading com www bmr trading com ...

Page 21: ...s xxx xxx xxx xxx port 21 IP of PLA44 xxx xxx xxx xxx port 21 router public IP address xxx xxx xxx xxx port 50000 50005 IP of PLA34 xxx xxx xxx xxx port 50000 50005 Notice Number of port of 80 21 is possible change on router Range of ports 50000 50005 is fixed and it is not possible to change it On the PLA34 device it is necessary set following parameters in IP public FTP 21 factory value user nam...

Page 22: ...ximum input voltage 24 VDC Maximum input consumption 10 mA Voltage transformer ratio 1 750 000 Current transformer ratio 1 750 000 Supply voltage power cuts memory 15 events Sampling rate 40 kHz Events trigger 10 ms Data memory for measured parameters 1 GB Display type and size LCD Communication port RS485 optional Modbus RTU 9 6 19 2 38 4 115 kBd Ethernet RJ45 10 100 Mbit USB Type B Temperature l...

Reviews: