7.3.4. Transient
Transient setting is defined by several parameters listed in table beneath.
Parameter
Description
Factory setting
Setting range
Absolute transient
Absolute transient activation
No
YES / NO
Absolute threshold
Threshold absolute transient setting
110%
100 ... 500%
Difference transient
Difference transient activation
No
YES / NO
Difference threshold
Threshold difference transient setting
20%
1 ... 100%
Increase time
Time delay before next transient recording after transient start
5s
1 ... 20 s
Increase value
Increment value for transient insensitivity after recording start
10V
1 ... 750000 V
Post samples
Number of recorded samples after the transient start
768
0 ... 8000
Pre samples
Number of recorded samples before the transient start
768
0 ... 8000
Memory for capturing the transients amplitude is fixed on the maximum of 8000 samples. Definition of number Pre
and Post samples is limited by this maximum samples memory space.