P_C2
Input EL2 (kVARh+ reactive consumption)
0
P_C3
Input EL3 (kVARh- reactive consumption)
0
P_C4
Input EL4 (kWh- active distribution, if SEL4=0 is set)
0
rELE
r_1 to r_6
Parameter setting of individual output relays R1-R6
uSE
Setting of relay usage 1 (yes - used), 0 (no - unused)
0 / 1
1
Prio
Setting of relay priority – value from 1 to 6. Higher priority means that
relay connects later and disconnects earlier. Appropriate circuit is
connected and disconnected less commonly.
1 ... 6
1-6
t_i
Minimum time of relay connection [min].
0 ... 15
1
t_o
Minimum time of relay disconnection before it can be switch on again
[min].
0 ... 15
1
nSEP
Flag of „not connected relay“. Used in the case when some of controlled
circuits is impossible to be disconnected, because of technological or
other reasons, even during exceeding of set maximum regulation value.
Values: 0 - relay is connecting according to regulation procedure; 1 -
relay is disabled and not used for regulation.
0 / 1
0
ESEP
Flag that it is possible to switch relay on even in case that time of
minimum disconnection has not expired yet. This flag is applied only at
moment, when actual consumption (during 1/4 hour) gets over the
requested maximum regulation level (minus hysteresis). Values: 1 - relay
is possible to connect before time; 0 - relay is waiting for expiration of
minimum disconnection time period.
0 / 1
1
t_m
Maximum time of stage disconnection [min]
0 ... 15
0
r_C
Regulation constants for regulation curve (see graph of regulation
principle)
P1
Threshold value of limitation curve for relay disconnecting
0 ... 80%
0
P2
Threshold value of limitation curve for relay connection
0 ... 80%
10
HYSt
Hysteresis – zone of protection against maximum regulated value
overrun
5 ... 20%
10
YEAr
Actual year setting.
2002
dAt
Actual date setting. Set parameter is blinking.
01.01
CAS
Actual time setting. At the first hour is set and then after pressing of
button
SET
, minutes are set too.
00:00
SEL4
Function setting of input No. 4. Value:
0 - input counts pulses from energy meter
1 - low tariff change is made by positive level of input No. 4
2 - low tariff change is made by negative level of input No. 4
0 / 1 / 2
0
SYnC
Real time synchronization by quarter hour pulse. Value:
1 – time is synchronized
0 – time is not synchronized
0 / 1
1
u1_4
Setting of active level of quarter hour pulse. Value:
0 – negative quarter hour pulse
1 – positive quarter hour pulse
2 – internal quarter hour pulse
0 / 1 / 2
1
P1_4
Moving forward to the new quarter hour. Value:
1 – all circuit switch on again (relays disconnect)
0 – circuits switch on according to the regulation conditions
0 / 1 / 2
1
dEL
Erasing and creating of the new measuring profile (last 40 days
measuring saved into the memory will be erased). It is necessary to
confirm this command by simultaneous pressing of buttons ►
+
<SET>+<MAN>
i_r
Regulation interval [sec]. Defines regulation speed.
1 ... 99
10