background image

Manual 2100-537

I

  

Page 

27 of 54

GROUND  WATER   

(WELL SYSTEM APPLICATIONS)

NOTE:

 

Unit shipped from factory with 60 PSIG low pressure 
switch wired into control circuit for ground water 
applications.

WATER CONNECTIONS

It is very important that an adequate supply of clean, non-

corrosive water at the proper pressure be provided before 

the installation is made.  Insufficient water, in the heating 

mode for example, will cause the low pressure switch to 

trip, shutting down the heat pump.  In assessing the capacity 

of the water system, it is advisable that the complete water 

system be evaluated to prevent possible lack of water or 

water pressure at various household fixtures whenever the 

heat pump turns on.  All plumbing to and from the unit is to 

be installed in accordance with local plumbing codes.  The 

use of plastic pipe, where permissible, is recommended to 

prevent electrolytic corrosion of the water pipe.  Because 

of the relatively cold temperatures encountered with well 

water, it is strongly recommended that the water lines 

connecting the unit be insulated to prevent water droplets 

from condensing on the pipe surface.
Refer to piping, Figure 11.  Slow open/close with 

End  

Switch (2)

, 24V, provides on/off control of the water flow to 

the unit.  Refer to the wiring diagram for correct hookup of 

the valve solenoid coil.

Constant Flow Valve (3)

 provides correct flow of water to 

the unit regardless of variations in water pressure.  Observe 

the water flow direction indicated by the arrow on the side 

of the valve body.  Following is a table showing which 

valve is to be installed with which heat pump.

Strainer (8) 

installed upstream of 

water coil inlet 

to collect 

foreign material which would clog the flow valve orifice.
The figure shows the use of 

shutoff valves (4) 

and

 (5)

, on 

the in and out water lines to permit isolation of the unit from 

the plumbing system should future service work require this.  

Globe valves should not be used as shutoff valves because 

of the excessive pressure drop inherent in the valve design.  

Instead use gate or ball valves as shutoffs, so as to minimize 

pressure drop.

Hose bib (6) 

and

 (7)

, and tees should be included to permit 

acid cleaning the refrigerant-to-water coil should such 

cleaning be required.  See WATER CORROSION.

Hose bib (1)

 provides access to the system to check water 

flow through the constant flow valve to insure adequate 

water flow through the unit.  A water meter is used to check 

the water flow rate.

WELL PUMP SIZING

Strictly speaking, sizing the well pump is the responsibility 

of the well drilling contractor.  It is important, however, 

that the HVAC contractor be familiar with the factors that 

determine what size pump will be required.  Rule of thumb 

estimates will invariably lead to under or oversized well 

pumps.  Undersizing the pump will result in inadequate 

water to the whole plumbing system, but with especially bad 

results to the heat pump –  NO HEAT / NO COOL calls will 

result.  Oversized pumps will short cycle and could cause 

premature pump motor or switch failures.
The well pump must be capable of supplying enough water 

and at an adequate pressure to meet competing demands of 

water fixtures.  The well pump must be sized in such a way 

that three requirements are met:

 

1.  Adequate flow rate in GPM.

 

2.  Adequate pressure at the fixture.

 

3.  Able to meet the above from the depth of the  

 

well-feet of lift.

TABLE  8

CONSTANT FLOW VALVES

(1) 

The pressure drop through the constant flow valve will 

vary depending on the available pressure ahead of the valve.  

Unless minimum of 15 psig is available 

immediately

 ahead 

of the valve, no water will flow.

Part No.

Min. Available 

Pressure PSIG

Flow Rate

GPM

CFV-5

15 (1)

5

CFV-6

15 (1)

6

CFV-7

15 (1)

7

CFV-9

15 (1)

9

CFV-10

15 (1)

10

Summary of Contents for GTA3600UD1-A

Page 1: ...TER SOURCE HEAT PUMP MODELS GTB1 A Blower Section GTA3600UD1AA Coil Section GTA4860UD1AA Coil Section GTADP 3642 B Coil Section GTADP 3642 C Coil Section GTADP 4860 C Coil Section GTC36S2 ADCX Compres...

Page 2: ...mponents 47 Compressor Solenoid 47 Troubleshooting GE ECM 2 3 Motors 48 49 Troubleshooting Table 50 Power Connector Table 50 Ground Source Heat Pump Performance Report 51 52 Wiring Diagrams 53 54 Figu...

Page 3: ...rocedures for Ground Source IGSHPA Heat Pump Systems Soil and Rock Classification for IGSHPA the Design of Ground Coupled Heat Pump Systems Ground Source Installation Standards IGSHPA Closed Loop Geot...

Page 4: ...P Advanced Distributor Products 3642 3 Ton 4860 4 5 Ton Geo Trio Fossil Fuel A Coil Section GT A 3600 UD 1 A A Revision Level Series A Coil Section Geo Trio 3600 3 Ton 4860 4 5 Ton A E Coated Coils Op...

Page 5: ...PPLICATION MODELS GTC36S2 GTC48S2 GTC60S2 Ground Loop 15 Methanol Propylene Glycol etc 8 12 15 Ground Water 6 7 9 Water Loop Cooling Tower 9 2 12 1 14 3 MODEL GTC36S2 GTC48S2 GTC60S2 Electrical Rating...

Page 6: ...ID Ft Hd 3 0 1 0 23 4 0 5 1 15 0 9 2 08 5 1 2 2 77 1 4 3 23 6 1 7 3 92 2 3 5 31 7 2 3 5 31 3 2 7 38 2 4 61 8 3 1 7 15 4 1 9 46 2 5 5 77 9 4 1 9 46 5 1 11 77 3 2 7 38 10 6 1 14 07 3 9 9 00 11 7 1 16 38...

Page 7: ...RAIN K O HORIZ OVERFLOW K O SUCTION CONNECTION LIQUID CONNECTION OVERFLOW MAIN DRAIN 19 15 16 3 1 2 21 5 8 2 3 16 CONDENSATE OVERFLOW WIRES 27 15 16 13 5 8 1 13 16 22 30 20 50 000 125 WIDTH 16 13 000...

Page 8: ...ONNECTION MAIN DRAIN SUCTION CONNECTION OVERFLOW LIQUID OVERFLOW F A E C 6 1 16 TYP 5 1 4 D 1 5 8 3 4 G FOSSIL FUEL ADP COIL SECTION DIMENSIONS MIS 3119 FIGURE 1B GTADP DIMENSION GTADP 3642 B GTADP 36...

Page 9: ...C GTB1 A BLOWER SECTION DIMENSIONS 15 5 8 24 9 16 MIS 2819 30 13 1 4 16 3 8 LOW VOLTAGE ENTRANCE OPENING ON BOTH SIDES OPTIONAL SIDE RETURN HIGH VOLTAGE K O FOR REMOTE APPLICATIONS ONLY 3 5 8 18 13 16...

Page 10: ...8 GTC60S2 18 1 2 3 3 4 DESUPERHEATER WATER OUT LIQUID LINE SUCTION LINE WATER IN WATER OUT DESUPERHEATER WATER IN 12 1 4 3 9 5 8 B 2 1 2 23 1 16 1 7 8 16 1 16 6 15 16 A 1 3 4 22 1 16 30 HIGH VOLTAGE U...

Page 11: ...ECTIONS 65 5 8 30 21 23 21 5 8 3 4 31 1 4 TOP DUCT OUTLET FLANGE 27 15 16 19 13 16 SECURE SECTIONS TOGETHER USING BOLT PART 1012 015 AND WASHER PART 1012 109 MAIN DRAIN OUTLET INLET OVERFLOW DRAIN OUT...

Page 12: ...age Entrance Low Voltage Entrance Top View 30 4 31 1 4 18 3 1 4 2 1 1 3 1 3 4 8 Front View 7 27 8 19 7 8 Opening Evaporator Opening Blower Right Side View 24 15 17 1 8 Overflow Drain Outlet Outlet Mai...

Page 13: ...Cond Coil Position Cond Coil Water Out Desuper Water In Desuper Water In Water Out Supply Return Return Secondary Return Drain Main Drain Blower in Shipped Position 7 8 Line Set Control Panel MIS 2828...

Page 14: ...Coil Water Out Cond Coil Water In Desuper Water In Water Out Secondary Main Drain Refrigerant Return Refrigerant Connections Refrigerant Connections Connections Refrigerant Connections Air Filter Req...

Page 15: ...plate that was removed in Step 3 above Step 7 Remove bottom rear fill plate from bottom front fill plate discard rear and resecure front fill plate into unit base and front of blower Step 8 Replace GT...

Page 16: ...WER AND SLIDE BLOWER OUT OF CABINET 1 SECURING BLOWER TO FRONT FILL PLATE REINSTALL 2 SCREWS REINSTALL BOTH FRONT PANELS 5 4 6 2 REMOVE 2 SCREWS FROM FRONT FILL PLATE AND SLIDE BACK FILL PLATE OUT OF...

Page 17: ...BOTH PLUG BLOWER POWER CONNECTOR INTO POWER PLUG PROTRUDING THROUGH MOUNT FIELD SUPPLIED SINGLE GANG ELECTRICAL BOX ALIGNED OVER HIGH VOLTAGE K O MIS 2843 REMOVE SUPPLIED WIRE HARNESS AND STRAIN RELI...

Page 18: ...ank Place the unit on a solid base preferably concrete to minimize undesirable noise and vibration DO NOT elevate the base pan on rubber or cork vibration eliminator pads as this will permit the unit...

Page 19: ...able 6 Filter Sizing Chart Page 19 matching your airflow and filter configuration to determine proper filter sizing CONDENSATE DRAIN Drain lines must be installed according to local plumbing codes It...

Page 20: ...200 2000 10 X 20 X 1 1 39 1 Pleated Filter 425 700 Not Recommended 12 X 24 X 1 2 00 600 1000 14 X 20 X 1 1 94 590 980 14 X 25 X 1 2 43 730 1215 16 X 20 X 1 2 22 670 1115 16 X 25 X 1 2 78 840 1400 20 X...

Page 21: ...RFLOW AIRFLOW SINGLE FILTER MIS 2882 AIR FILTER CENTRAL RETURN GRILLE S ONE OR MULTIPLE MIS 2883 ONE OR MULTIPLE CENTRAL RETURN GRILLE S AIR FILTER SIDE INLET S ONE OR BOTH SIDES OR IN COMBINATION WIT...

Page 22: ...l need attached to the reference points accordingly Example 1 Control Circuit transformer rated at 50 VA 2 Maximum total distance of control circuit wiring 85 feet From Table 7 minimum of 16 gauge wir...

Page 23: ...White Black White Green Use With Water Green Red Motorized Valve Without End Switch Motorized Valve With End Switch Use with Water Black A Thermostat A B Low Voltage Connection Diagram B O B Y2 L G Y...

Page 24: ...stems The design eliminates most causes of system failure The heat pump itself is rarely the cause Most problems occur because designers and installers forget that a ground loop earth coupled heat pum...

Page 25: ...e actual flow rate If the flow rate is too low recheck the selection of the loop pump module model for sufficient capacity If the module selection is correct there is probably trapped air or a restric...

Page 26: ...537G Page 25 of 52 0 10 20 30 40 50 60 70 0 5 10 15 20 25 30 35 Flow GPM Head Feet FIGURE 10 PERFORMANCE MODEL DORFC 2 FLOW CENTER 0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 Flow GPM Head Feet FIGUR...

Page 27: ...valves 4 and 5 on the in and out water lines to permit isolation of the unit from the plumbing system should future service work require this Globe valves should not be used as shutoff valves because...

Page 28: ...included in Manual 2100 078 should guarantee that the well pump has enough capacity It should also ensure that the piping is not undersized which would create too much pressure due to friction loss H...

Page 29: ...p application Will there be enough water And how will the water quality affect the system Water quantity is an important consideration and one which is easily determined The well driller must perform...

Page 30: ...Figure 12 The acid solution can be introduced into the heat pump coil through the hose bib A Be sure the isolation valves are closed to prevent contamination of the rest of the system by the coil The...

Page 31: ...tic or corrugated for water return to the lake or pond I The drain line discharge should be located at least 100 feet from the dry well location J The drain line should be installed with a slope of 2...

Page 32: ...ater heaters must be a two tank installation Tanks specifically intended for hot water storage are available from water heater manufacturers solar hot water storage tanks A well insulated electric wat...

Page 33: ...istors ensure there is at least 2 positive differential between entering leaving water temperatures and will shut down the pump accordingly START UP AND CHECK OUT Be sure all shut off valves are open...

Page 34: ...INLET Y R C 24VAC L N CONTROL LOGIC NO C 2 1 3 MIS 2844 C PUMP CONTROL BLACK BLACK FROM GEOTHERMAL LOGIC CONTROL RED RED BLACK RED RED DESUPERHEATER COMPRESSOR CONTACTOR SIGNAL LIMIT TEMPERATURE MOTO...

Page 35: ...GH PRESSURE RELIEF VALVE HIGH PRESSURE RELIEF VALVE HOT WATER TO HOUSE COLD WATER IN STRAINER DRAIN SHUTOFF VALVES OUT IN OUT IN WATER SOURCE UNIT NOTES DO NOT OPERATE PUMP WITHOUT WATER LINES CONNECT...

Page 36: ...LLED WATER HEATER WHEN WATER STORAGE IS INSTALLED IN VERTICAL ALL PLUMBING MUST CONFORM TO LOCAL CODES INSTALLED AT BOTTOM AS SHOWN POSITION PIPING TO IN SIDE OF PUMP MUST BE MIS 2832 OUT PER CODES CH...

Page 37: ...ergize the pump relay inclusive on the control board A It will constantly monitor inputs from two temperature sensors Inlet Outlet water sensors B It will constantly monitor the Y signal C Upon acknow...

Page 38: ...eing energized Additionally what happens the thermostat completes a circuit from R to Y2 This sends a signal to both the staging solenoid on the side of the compressor and sends a signal to the Blower...

Page 39: ...delay random start If fault reoccurs or didn t clear the first time after 30 seconds the control will go into hard lockout and will energize the L output signal SEQUENCE OF OPERATION UNDER OVER VOLTAG...

Page 40: ...SOR DESUPERHEATER COIL EXPANSION VALVE LOW PRESSURE SWITCHES WATER COIL HIGH PRESSURE SWITCH PUMP MODULE HIGH VOLTAGE UNIT HIGH VOLTAGE MIS 2838 GEOTHERMAL LOGIC CONTROL CAPACITOR COMPRESSOR DESUPERHE...

Page 41: ...Manual 2100 537I Page 41 of 54 FIGURE 19...

Page 42: ...line set length Or you can specifically measure your line set length and add 1 4 ounces of R 410A refrigerant per 1 of line set length REFRIGERANT FITTING ATTACHMENT 1 Coat all mating surface includi...

Page 43: ...Pre charge the line set and coil with refrigerant before screwing the refrigerant fittings onto the pre charged condenser section REFRIGERANT CHARGE QUANTITY Line Set and Evaporator Coil GTADPAdd On...

Page 44: ...composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charg...

Page 45: ...Entering Water Coil F 30 F 35 F 40 F 45 F 50 F 55 F 60 F 65 F 70 F 75 F 80 F 85 F 90 F 95 F 100 F 105 F 110 F GTC36S2 75 DB 62 WB Low Side High Side 116 130 119 144 121 159 123 173 126 188 128 202 13...

Page 46: ...ume Low Air Filters Dirty Undersized or Restricted Ductwork Auxillary Heat Upstream of Coil Compressor Will Not Run No Power at Contactor Compressor Will Not Run Power at Contactor Compressor Hums But...

Page 47: ...t control circuit voltage must be 18 to 28 volts ac The coil power requirement is 20 VA The external electrical connection is made with a molded plug assembly This plug contains a full wave rectifier...

Page 48: ...f it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Che...

Page 49: ...rol module is now completely detached from the motor Verify with a standard ohmmeter that the resistance from each motor lead in the motor plug just removed to the motor shell is 100K ohms Refer to Fi...

Page 50: ...in 1 24 VAC C Common Signal Always Energized Pin 2 X X Pin 3 24 VAC C Common Signal Always Energized Pin 4 Delay Tap Profiles Varied Half Wave Signals Based Upon Settings Pin 5 Cool Tap Select Tables...

Page 51: ...Open Loop System Water Well Closed Loop System A If Open Loop where is water discharged 8 The following questions are for Closed Loop systems only A Closed loop system designed by B Type of antifreez...

Page 52: ...minal A 20 Suction line temperature 6 from compressor F 21 Superheat at compressor F 22 Liquid line temperature at metering device F 23 Coil subcooling F INDOOR SIDE DATA Cooling Heating 24 Dry bulb t...

Page 53: ...13 14 12 10 11 9 2 8 3 7 208 230 60 1 4 5 6 YELLOW BLACK BLACK WHITE BROWN BLACK WHITE GRAY 2 8 BLUE BLACK YELLOW OFF OFF CIRCUIT CONTROL PLUG FIELD CONNECTIONS TO THERMOSTAT SWITCH 1 BLACK COM OFF TR...

Page 54: ...YELLOW YELLOW YELLOW YELLOW RED YELLOW YELLOW RED GREEN BROWN WHITE BROWN WHITE COMPRESSOR STAGING SOLENOID REVERSING VALVE SOLENOID 24 VAC FROM AIR HANDLING UNIT COND Yellow fault light illuminated...

Reviews: