background image

Manual 2100-537

I

 

Page 

18 of 54

For installations requiring the continued use of an 

existing gas or oil fired furnace, add-on cased “A” coils 

are available.  Two 3-ton coils designed to fit standard 

“B” and “C” width furnaces and one 4/5 ton coil 

designed for a “C” cabinet are available.  Refer to Page 

4 of this manual for the model nomenclature and the 

specification sheet for performance data.

For top discharge oil furnaces, the coil drain pan MUST 

be located a minimum of 6 inches above the top of 

the furnace cabinet.  Two coil spacer accessories are 

available to fit Bard oil furnaces:

  CSADP2220  22" x 20" x 6"

  All models except 140,000 Btu Low-Boy
  CASDP2520 25" x 20" x 6"

  140,000 Btu Low-Boy only

For all other brands, a coil support system must be field 

fabricated to maintain the 6" spacing.

APPLICATION AND LOCATION

       

WARNING

In applying a duct heater, refer to duct heater installation 

instructions for minimum clearance to combustible materials, 

maximum allowed inlet air temperatures, and minimum air 

volume requirements for KW usage.

DUAL FUEL HEATING / COOLING

Dual fuel is the combination of a fossil fuel furnace, normally 

gas or oil, with a heat pump.  In milder weather the heat pump 

uses the available outdoor warmth and will transport that heat 

into your house cheaper than burning gas or oil.  When it gets 

very cold, around 35 degrees F., the heat pump automatically 

shuts down and the furnace heats the home.  This combination 

gives you the maximum savings on both heating and cooling 

while providing you with ideal indoor comfort.
Dual fuel systems are becoming increasingly popular in lieu 

of conventional high efficiency furnaces with air conditioning 

due to the energy savings and ease of installation.  Today’s 

new hi-tech thermostats eliminate the need for complicated 

wiring and duel fuel control boards.  Bard recommends 

using the Honeywell THX9321R5030 Prestige® Thermostat 

(Does not include outdoor sensor).  Honeywell also offers 

the Prestige® Kit 2.0 which includes the THX9321R5030 

Prestige® Thermostat, REM5000R1001 Portable Comfort 

Control and C7089R1013 Wireless Outdoor Sensor.

LOCATION

The unit may be installed in a basement, closet, or utility room 

provided adequate service access is ensured.  
These units are not approved for outdoor installation 

and therefore must be installed inside the structure being 

conditioned.  

Do not locate in areas subject to freezing in the 

winter or subject to sweating in the summer.

Before setting the unit, consider ease of piping, drain and 

electrical connections for the unit.  Also, for units which will 

be used with a desuperheater unit, consider the proximity of 

the unit to the water heater or storage tank.  Place the unit on a 

solid base, preferably concrete, to minimize undesirable noise 

and vibration.  

DO NOT 

elevate the base pan on rubber or 

cork vibration eliminator pads as this will permit the unit base 

to act like a drum, transmitting objectionable noise.

DUCTWORK

If the unit is to be installed in a closet or utility room which 

does not have a floor drain, a secondary drain pan under the 

entire unit is highly recommended.

DO NOT

 install the unit in such a way that a direct path exists 

between any return grille and the unit.  Rather, insure that the 

air entering the return grille will make at least one turn before 

entering the unit or coil.  This will reduce possible objectionable 

compressor and air noise from entering the occupied space.
Design the ductwork according to methods given by the 

Air Conditioning Contractors of America.  When duct runs 

through unconditioned spaces, it should be insulated with 

vapor barrier.  It is recommended that flexible connections be 

used to connect the ductwork to the unit in order to keep the 

noise transmission to a minimum.

GENERAL

The GT Series Geothermal Heat Pumps feature three sections 

(GTA - Air Coil Section, GTB - Blower Section and GTC - 

Compressor Section) which cover upflow (bottom, right/left-

side return), counterflow and horizontal (left and right-hand 

discharge) applications.
The individual sections are shipped internally wired, requiring 

duct connections, thermostat wiring, 230/208 volt AC power 

wiring, refrigerant line connections and water piping.  The 

equipment covered in this manual is to be installed by trained, 

experienced service and installation technicians.

These instructions and any instructions packaged with any 

separate equipment required to make up the entire heat 

pump system should be carefully read before beginning the 

installation.  Note particularly any tags and/or labels attached 

to the equipment. 
While these instructions are intended as a general 

recommended guide, they do not in any way supersede any 

national and/or local codes.  Authorities having jurisdiction 

should be consulted before the installation is made.

SHIPPING DAMAGE

Upon receipt of the equipment, the carton should be checked 

for external signs of shipping damage.  If damage is found, 

the receiving party must contact the last carrier immediately, 

preferably in writing, requesting inspection by the carrier’s agent.

APPLICATION

Capacity of the unit for a proposed installation should be 

based on heat loss calculations made in accordance with 

methods of the Air Conditioning Contractors of America.  

The air duct system should be sized and installed in 

accordance with Standards of the National Fire Protection 

Association for the Installation of Air Conditioning and 

Venting systems of Other than Residence Type NFPA 

No. 90A, and residence Type Warm Air Heating and Air 

Conditioning Systems, NFPA No. 90B.

Summary of Contents for GTA3600UD1-A

Page 1: ...TER SOURCE HEAT PUMP MODELS GTB1 A Blower Section GTA3600UD1AA Coil Section GTA4860UD1AA Coil Section GTADP 3642 B Coil Section GTADP 3642 C Coil Section GTADP 4860 C Coil Section GTC36S2 ADCX Compres...

Page 2: ...mponents 47 Compressor Solenoid 47 Troubleshooting GE ECM 2 3 Motors 48 49 Troubleshooting Table 50 Power Connector Table 50 Ground Source Heat Pump Performance Report 51 52 Wiring Diagrams 53 54 Figu...

Page 3: ...rocedures for Ground Source IGSHPA Heat Pump Systems Soil and Rock Classification for IGSHPA the Design of Ground Coupled Heat Pump Systems Ground Source Installation Standards IGSHPA Closed Loop Geot...

Page 4: ...P Advanced Distributor Products 3642 3 Ton 4860 4 5 Ton Geo Trio Fossil Fuel A Coil Section GT A 3600 UD 1 A A Revision Level Series A Coil Section Geo Trio 3600 3 Ton 4860 4 5 Ton A E Coated Coils Op...

Page 5: ...PPLICATION MODELS GTC36S2 GTC48S2 GTC60S2 Ground Loop 15 Methanol Propylene Glycol etc 8 12 15 Ground Water 6 7 9 Water Loop Cooling Tower 9 2 12 1 14 3 MODEL GTC36S2 GTC48S2 GTC60S2 Electrical Rating...

Page 6: ...ID Ft Hd 3 0 1 0 23 4 0 5 1 15 0 9 2 08 5 1 2 2 77 1 4 3 23 6 1 7 3 92 2 3 5 31 7 2 3 5 31 3 2 7 38 2 4 61 8 3 1 7 15 4 1 9 46 2 5 5 77 9 4 1 9 46 5 1 11 77 3 2 7 38 10 6 1 14 07 3 9 9 00 11 7 1 16 38...

Page 7: ...RAIN K O HORIZ OVERFLOW K O SUCTION CONNECTION LIQUID CONNECTION OVERFLOW MAIN DRAIN 19 15 16 3 1 2 21 5 8 2 3 16 CONDENSATE OVERFLOW WIRES 27 15 16 13 5 8 1 13 16 22 30 20 50 000 125 WIDTH 16 13 000...

Page 8: ...ONNECTION MAIN DRAIN SUCTION CONNECTION OVERFLOW LIQUID OVERFLOW F A E C 6 1 16 TYP 5 1 4 D 1 5 8 3 4 G FOSSIL FUEL ADP COIL SECTION DIMENSIONS MIS 3119 FIGURE 1B GTADP DIMENSION GTADP 3642 B GTADP 36...

Page 9: ...C GTB1 A BLOWER SECTION DIMENSIONS 15 5 8 24 9 16 MIS 2819 30 13 1 4 16 3 8 LOW VOLTAGE ENTRANCE OPENING ON BOTH SIDES OPTIONAL SIDE RETURN HIGH VOLTAGE K O FOR REMOTE APPLICATIONS ONLY 3 5 8 18 13 16...

Page 10: ...8 GTC60S2 18 1 2 3 3 4 DESUPERHEATER WATER OUT LIQUID LINE SUCTION LINE WATER IN WATER OUT DESUPERHEATER WATER IN 12 1 4 3 9 5 8 B 2 1 2 23 1 16 1 7 8 16 1 16 6 15 16 A 1 3 4 22 1 16 30 HIGH VOLTAGE U...

Page 11: ...ECTIONS 65 5 8 30 21 23 21 5 8 3 4 31 1 4 TOP DUCT OUTLET FLANGE 27 15 16 19 13 16 SECURE SECTIONS TOGETHER USING BOLT PART 1012 015 AND WASHER PART 1012 109 MAIN DRAIN OUTLET INLET OVERFLOW DRAIN OUT...

Page 12: ...age Entrance Low Voltage Entrance Top View 30 4 31 1 4 18 3 1 4 2 1 1 3 1 3 4 8 Front View 7 27 8 19 7 8 Opening Evaporator Opening Blower Right Side View 24 15 17 1 8 Overflow Drain Outlet Outlet Mai...

Page 13: ...Cond Coil Position Cond Coil Water Out Desuper Water In Desuper Water In Water Out Supply Return Return Secondary Return Drain Main Drain Blower in Shipped Position 7 8 Line Set Control Panel MIS 2828...

Page 14: ...Coil Water Out Cond Coil Water In Desuper Water In Water Out Secondary Main Drain Refrigerant Return Refrigerant Connections Refrigerant Connections Connections Refrigerant Connections Air Filter Req...

Page 15: ...plate that was removed in Step 3 above Step 7 Remove bottom rear fill plate from bottom front fill plate discard rear and resecure front fill plate into unit base and front of blower Step 8 Replace GT...

Page 16: ...WER AND SLIDE BLOWER OUT OF CABINET 1 SECURING BLOWER TO FRONT FILL PLATE REINSTALL 2 SCREWS REINSTALL BOTH FRONT PANELS 5 4 6 2 REMOVE 2 SCREWS FROM FRONT FILL PLATE AND SLIDE BACK FILL PLATE OUT OF...

Page 17: ...BOTH PLUG BLOWER POWER CONNECTOR INTO POWER PLUG PROTRUDING THROUGH MOUNT FIELD SUPPLIED SINGLE GANG ELECTRICAL BOX ALIGNED OVER HIGH VOLTAGE K O MIS 2843 REMOVE SUPPLIED WIRE HARNESS AND STRAIN RELI...

Page 18: ...ank Place the unit on a solid base preferably concrete to minimize undesirable noise and vibration DO NOT elevate the base pan on rubber or cork vibration eliminator pads as this will permit the unit...

Page 19: ...able 6 Filter Sizing Chart Page 19 matching your airflow and filter configuration to determine proper filter sizing CONDENSATE DRAIN Drain lines must be installed according to local plumbing codes It...

Page 20: ...200 2000 10 X 20 X 1 1 39 1 Pleated Filter 425 700 Not Recommended 12 X 24 X 1 2 00 600 1000 14 X 20 X 1 1 94 590 980 14 X 25 X 1 2 43 730 1215 16 X 20 X 1 2 22 670 1115 16 X 25 X 1 2 78 840 1400 20 X...

Page 21: ...RFLOW AIRFLOW SINGLE FILTER MIS 2882 AIR FILTER CENTRAL RETURN GRILLE S ONE OR MULTIPLE MIS 2883 ONE OR MULTIPLE CENTRAL RETURN GRILLE S AIR FILTER SIDE INLET S ONE OR BOTH SIDES OR IN COMBINATION WIT...

Page 22: ...l need attached to the reference points accordingly Example 1 Control Circuit transformer rated at 50 VA 2 Maximum total distance of control circuit wiring 85 feet From Table 7 minimum of 16 gauge wir...

Page 23: ...White Black White Green Use With Water Green Red Motorized Valve Without End Switch Motorized Valve With End Switch Use with Water Black A Thermostat A B Low Voltage Connection Diagram B O B Y2 L G Y...

Page 24: ...stems The design eliminates most causes of system failure The heat pump itself is rarely the cause Most problems occur because designers and installers forget that a ground loop earth coupled heat pum...

Page 25: ...e actual flow rate If the flow rate is too low recheck the selection of the loop pump module model for sufficient capacity If the module selection is correct there is probably trapped air or a restric...

Page 26: ...537G Page 25 of 52 0 10 20 30 40 50 60 70 0 5 10 15 20 25 30 35 Flow GPM Head Feet FIGURE 10 PERFORMANCE MODEL DORFC 2 FLOW CENTER 0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 Flow GPM Head Feet FIGUR...

Page 27: ...valves 4 and 5 on the in and out water lines to permit isolation of the unit from the plumbing system should future service work require this Globe valves should not be used as shutoff valves because...

Page 28: ...included in Manual 2100 078 should guarantee that the well pump has enough capacity It should also ensure that the piping is not undersized which would create too much pressure due to friction loss H...

Page 29: ...p application Will there be enough water And how will the water quality affect the system Water quantity is an important consideration and one which is easily determined The well driller must perform...

Page 30: ...Figure 12 The acid solution can be introduced into the heat pump coil through the hose bib A Be sure the isolation valves are closed to prevent contamination of the rest of the system by the coil The...

Page 31: ...tic or corrugated for water return to the lake or pond I The drain line discharge should be located at least 100 feet from the dry well location J The drain line should be installed with a slope of 2...

Page 32: ...ater heaters must be a two tank installation Tanks specifically intended for hot water storage are available from water heater manufacturers solar hot water storage tanks A well insulated electric wat...

Page 33: ...istors ensure there is at least 2 positive differential between entering leaving water temperatures and will shut down the pump accordingly START UP AND CHECK OUT Be sure all shut off valves are open...

Page 34: ...INLET Y R C 24VAC L N CONTROL LOGIC NO C 2 1 3 MIS 2844 C PUMP CONTROL BLACK BLACK FROM GEOTHERMAL LOGIC CONTROL RED RED BLACK RED RED DESUPERHEATER COMPRESSOR CONTACTOR SIGNAL LIMIT TEMPERATURE MOTO...

Page 35: ...GH PRESSURE RELIEF VALVE HIGH PRESSURE RELIEF VALVE HOT WATER TO HOUSE COLD WATER IN STRAINER DRAIN SHUTOFF VALVES OUT IN OUT IN WATER SOURCE UNIT NOTES DO NOT OPERATE PUMP WITHOUT WATER LINES CONNECT...

Page 36: ...LLED WATER HEATER WHEN WATER STORAGE IS INSTALLED IN VERTICAL ALL PLUMBING MUST CONFORM TO LOCAL CODES INSTALLED AT BOTTOM AS SHOWN POSITION PIPING TO IN SIDE OF PUMP MUST BE MIS 2832 OUT PER CODES CH...

Page 37: ...ergize the pump relay inclusive on the control board A It will constantly monitor inputs from two temperature sensors Inlet Outlet water sensors B It will constantly monitor the Y signal C Upon acknow...

Page 38: ...eing energized Additionally what happens the thermostat completes a circuit from R to Y2 This sends a signal to both the staging solenoid on the side of the compressor and sends a signal to the Blower...

Page 39: ...delay random start If fault reoccurs or didn t clear the first time after 30 seconds the control will go into hard lockout and will energize the L output signal SEQUENCE OF OPERATION UNDER OVER VOLTAG...

Page 40: ...SOR DESUPERHEATER COIL EXPANSION VALVE LOW PRESSURE SWITCHES WATER COIL HIGH PRESSURE SWITCH PUMP MODULE HIGH VOLTAGE UNIT HIGH VOLTAGE MIS 2838 GEOTHERMAL LOGIC CONTROL CAPACITOR COMPRESSOR DESUPERHE...

Page 41: ...Manual 2100 537I Page 41 of 54 FIGURE 19...

Page 42: ...line set length Or you can specifically measure your line set length and add 1 4 ounces of R 410A refrigerant per 1 of line set length REFRIGERANT FITTING ATTACHMENT 1 Coat all mating surface includi...

Page 43: ...Pre charge the line set and coil with refrigerant before screwing the refrigerant fittings onto the pre charged condenser section REFRIGERANT CHARGE QUANTITY Line Set and Evaporator Coil GTADPAdd On...

Page 44: ...composition during multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charg...

Page 45: ...Entering Water Coil F 30 F 35 F 40 F 45 F 50 F 55 F 60 F 65 F 70 F 75 F 80 F 85 F 90 F 95 F 100 F 105 F 110 F GTC36S2 75 DB 62 WB Low Side High Side 116 130 119 144 121 159 123 173 126 188 128 202 13...

Page 46: ...ume Low Air Filters Dirty Undersized or Restricted Ductwork Auxillary Heat Upstream of Coil Compressor Will Not Run No Power at Contactor Compressor Will Not Run Power at Contactor Compressor Hums But...

Page 47: ...t control circuit voltage must be 18 to 28 volts ac The coil power requirement is 20 VA The external electrical connection is made with a molded plug assembly This plug contains a full wave rectifier...

Page 48: ...f it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Che...

Page 49: ...rol module is now completely detached from the motor Verify with a standard ohmmeter that the resistance from each motor lead in the motor plug just removed to the motor shell is 100K ohms Refer to Fi...

Page 50: ...in 1 24 VAC C Common Signal Always Energized Pin 2 X X Pin 3 24 VAC C Common Signal Always Energized Pin 4 Delay Tap Profiles Varied Half Wave Signals Based Upon Settings Pin 5 Cool Tap Select Tables...

Page 51: ...Open Loop System Water Well Closed Loop System A If Open Loop where is water discharged 8 The following questions are for Closed Loop systems only A Closed loop system designed by B Type of antifreez...

Page 52: ...minal A 20 Suction line temperature 6 from compressor F 21 Superheat at compressor F 22 Liquid line temperature at metering device F 23 Coil subcooling F INDOOR SIDE DATA Cooling Heating 24 Dry bulb t...

Page 53: ...13 14 12 10 11 9 2 8 3 7 208 230 60 1 4 5 6 YELLOW BLACK BLACK WHITE BROWN BLACK WHITE GRAY 2 8 BLUE BLACK YELLOW OFF OFF CIRCUIT CONTROL PLUG FIELD CONNECTIONS TO THERMOSTAT SWITCH 1 BLACK COM OFF TR...

Page 54: ...YELLOW YELLOW YELLOW YELLOW RED YELLOW YELLOW RED GREEN BROWN WHITE BROWN WHITE COMPRESSOR STAGING SOLENOID REVERSING VALVE SOLENOID 24 VAC FROM AIR HANDLING UNIT COND Yellow fault light illuminated...

Reviews: