27
L1
MAX 500
Ø100
MIN. 400
B
22
: Single pipe flue to outside wall or roof terminal. Combustion air from inside
building
INSTALLATION DISTANCES FOR FLUE PIPE:
HORIZONTAL FLUE
VERTICAL FLUE
TYPE UNIT
L1 MIN.
L1 MAX.
L2 MIN.
L2 MAX.
1
m 1,00
5,00
1,00
10,00
2
m 1,00
5,00
1,00
10,00
3
m 1,00
5,00
1,00
10,00
4
m 1,00
5,00
1,00
10,00
5
m 1,00
5,00
1,00
10,00
6
m 1,00
5,00
1,00
10,00
•
Only manufacturers recommended flue must be used
•
When designing the flue consideration should be made for entrapment and disposal of any condensate
•
Each bend corresponds to between 0,8-1 meter of horizontal pipework
•
The flue installation must comply with all the relevant regulations regarding height and position from all openings.
Ø100
MIN 400
L2