37
We reserve the right to make changes without any prior notice.
Translation from original instructions
Table 3 – Additional R410A refrigerant charges per metre of linear pipe
Outer Diameter [mm]
Gas [kg]
Liquid [kg]
10
0.0045
0.0474
12
0.007
0.074
14
0.01
0.1
16
0.014
0.145
18
0.018
0.19
22
0.028
0.3
28
0.048
0.5
* Discharge saturation temperature 45 ° C, liquid temperature 40 ° C
Suggested additional oil charge: over 20 metres of linear development of the pipes, add a quantity of oil equal
to 2% in weight of the total refrigerant present in the circuit. Refer to the type of oil indicated on the compres
-
sor’s label.
For two-circuit units featuring at least one inverter-controlled BLDC compressor pay attention to the type of oil loaded into
each cooling circuit.
-
Circuits fitted with a BLDC compressor (in single or twin configuration with ON/OFF compressor) use IDEMITSU FV50S
oil.
-
the circuit featuring ON/OFF compressors only uses EMKARARE RL 32 H oil.
If needed, do not forget to top up the level with the correct type of oil without mixing the two different oils, as
they are not compatible. Always use the oil recommended by the Manufacturer of the compressor or a perfect-
ly equivalent oil. The use of an incorrect type of oil may cause serious damage to the compressors and imme
-
diately void any guarantee.
Table 4 - Configurations
Relative
position of the
condensing
unit
Syphons on the
gas line
Liquid line
insulation
Gas line
insulation
Maximum
height
difference
between the
sections
Non-return
valve to the
condenser
Higher level con-
densing unit
Every 6 m of
vertical risers (5
m for circuits with
inverter-controlled
compressor)
Only in the case
of long stretches
exposed to sunli-
ght or to high room
temperatures
Necessary
30 m (15 m 7.1 -
12.1)
Recommended on
input
Lower level con-
densing unit
-
Only in the case
of long stretches
exposed to sunli-
ght or to high room
temperatures
Necessary inside
the building
8 m
Recommended on
output