To Enable Relay & Contacts:
1
Open the
App Drawer
2
Select
Outputs
3
Select
Relay & Contacts
4
Set
Desired Values
(refer to chart below)
!
Contact #1
!
Contact #2
!
Contact #3
!
Relay Output
5
Confirm by pressing
Save
9.0
Relay & Contacts
This feature is used to assign alarms to relay & contact closures
Four values to be defined:
1) Contact #1
2) Contact #2
3) Contact #3
4) Relay Output
Selection:
Contact energizes when:
Pump Run/Stop
Motor turning (roller assembly is rotating)
Monitor Input
Incoming analog or digital signal is not received or out of range
Monitor Output
Outgoing analog or digital signal not transmitted or out of range
Monitor Run/Fail
Motor fails to respond to commands
4-20 In Active
4-20mA mode is running
Frequency In Active
Frequency mode is running
Manual Speed Active
Manual Speed mode is running
Pulse In Active
Pulse In mode is running
Prime Active
Prime mode is running
FVS
After the programmed delay time pulses are not received from flow sensor.
TFD
Tube failure is detected by sensors in the head
Both TFD/FVS
Either TFD or FVS system triggers
®
FLEXFLO A3
9.0
Output Setup
Page 32