GFCI BRANCH AND ELCI MAIN
CIRCUIT BREAKER MOUNTING OPTIONS
Load Neutral (white)
Pigtail Wire (white)
Load
Neutral
(white)
Line
Hot
(black)
Line
Hot
(black)
Neutral
Bus
AC Power
Distribution
Panel
Source
ELCI INSTALLATION REVIEW
SAFETY INSTRUCTIONS:
1. Do not ground neutral wire on the load side of the ELCI.
2. Test once a month.
3. Do not reverse line and load connections.
INSTALLATION PROCEDURE:
1. Unplug shore power or turn off and lock out the power to
the enclosure in which the ELCI is to be installed.
2. Turn off the ELCI handle. Feed the load side (L1) hot
and (N) neutral wires through the opening in the
sensing coil. Connect to the appropriate load side
terminals of the circuit breaker. Connect corresponding
line side (source) wires directly to the Breaker
Line Terminals.
3. Connect the white pigtail neutral wire of the ELCI to
the panel load neutral bus bar or the load side neutral
terminal
(see below)
.
4. Mount ELCI to front panel and mount front panel to
enclosure
(may be mounted first, depending on installation)
.
5. Turn on power and turn on breaker handle.
6. Press test button to confirm trip and reset breaker.
7. Place Monthly Test Reminder label in a convenient
place near (or on) the panel.
For information about GFCI installation, please refer to
www.bluesea.com
See ELCI instruction