8.1.- Analog output port
PR200 can provide 1 channel analog output port, can provide 4 ~ 20mA signal to PLC or other
device, user can free to select the transmit electrical parameters: Ia, Ib, Ic, Iavg
Note
: Analog output port cannot be choosing with the ground fault protection function.
8.2.- Digital output port
PR200 can choose extra 2 channels digital output, the physical DO relay standard is 5A 250VAC /
5A 30VDC.
*Remote mode operation
In “Remote” mode, user can use function code 05 to trig single relay, device RS-485 port follow
MODBUS-RTU protocol, command as following:
Host inquiry:
01
05
00 01
FF 00
DD FA
Address
Code
No.1 Relay
register
Relay value
(FF00:close; 0000: open)
CRC
Slave answer:
01
05
00 01
FF 00
DD FA
Detail operation please refer to chart 5.5- Programming menu structure introduction