4”
20”
14”
5. STANDALONE SINGLE BUTTON DOCK ARRANGEMENT
X
UNDER DOCK
NOTE
: FUSED DISCONNECT
BY OTHERS
SINGLE PUSH BUTTON
CONTROL STATION
(MOUNTED & WIRED
BY OTHERS)
MAIN POWER
(TO CONTROL STATION)
ELECTRICAL REQUIREMENTS-
• MOUN
T CONTROL BOX STATION TO WALL
• FUSED DISCONNEC
T PROVIDED BY OTHERS AND WIRING BY OTHERS
• INS
TALL WIRING FROM CONTROL BOX STATION TO BLOWER MOTOR
• INS
TALL WIRING FROM CONTROL BOX STATION TO POWER SUPPLY
GROUND LEVEL
- ONE CONDUIT REQUIRED;
- INSTALL SECOND CONDUIT FOR FUTURE
EXPANSION (INTERLOCKS, COMBOS, ETC.)
NEW CONSTRUCTION (AIR DOCK):
1. RUN ONE 1/2” I.D. CONDUIT FROM THE CONTROL STATION TO THE BLOWER MOTOR JUNCTION BOX.
2. RUN ONE 1/2” I.D. CONDUIT FROM THE CONTROL STATION TO THE PIT FOR FUTURE EXPANSION (I.E.
INTERLOCKS, COMBOS, ETC.)
MINIMUM CONCRETE STRENGTH 3,000 P.S.I.
POWER WIRING
SINGLE PUSH BUTTON CONTROL STATION
(MOUNTED ON DRIVERS SIDE)
MAIN POWER
(from fused disconnect)
MOTOR WIRING
(to Blower Motor)
50”
!!!
DO NOT WIRE HIGH AND LOW VOLTAGES IN THE SAME CONDUIT.
High
voltage range is 115V and up. Lower voltages include the communication and
solenoid wiring as well as the I/O.
FRONT ELEVATION VIEW*
INSIDE BUILDING VIEW*
NOTE: *DRAWINGS NOT TO SCALE
MOTOR WIRING
(to single push button control station)
50”
AIR HOSE
U-SERIES AIRBAG DOCK LEVELER with SINGLE PUSH BUTTON CONTROLS
5