12.3 REPAIRING THE REFRIGERANT CIRCUIT
If repairs have been made to the refrigerant circuit, perform the following steps:
- leak test;
- vacuum and dehydration of refrigerant circuit;
- refrigerant charge.
If the circuit is to be emptied, use the appropriate equipment to collect
the refrigerant.
12.3.1 Leak test
Charge the refrigerant circuit to a pressure of 15 bar with dry nitrogen gas by means of a cylinder fitted with a
pressure reducer. Check the circuit for leaks with a leak detector. The formation of bubbles or foam indicates the
presence of leaks.
If leaks are found during the test, empty the refrigerant circuit and then repair the point of leakage by welding
with appropriate alloys.
Do not use oxygen instead of nitrogen: explosion hazard.
12.3.2 High vacuum and dehydration of the refrigerant circuit
To generate a high vacuum in the refrigerant circuit use a high vacuum pump able to reach 0.1 mbar of absolute
pressure with a flow rate of 10 m3/h. With this type of pump, a single vacuum cycle is normally sufficient to reach
an absolute pressure of 0.1 mbar.
If this type of pump is not available, or in the event that the circuit has been left open for a long period of time,
you are strongly advised to use the triple evacuation method. This procedure is also prescribed in the event of
moisture in the refrigerant circuit.
Connect the vacuum pump to the charge connector.
Proceed as follows:
- Evacuate the circuit to a pressure of at least 35 mbar absolute. Charge the circuit with nitrogen to a relative
pressure of approx. 1 bar.
- Repeat the operation described above.
- Repeat the operation described above for the third time in order to reach the highest degree of vacuum possible.
This procedure should guarantee the elimination of up to 99% of contaminants.
Summary of Contents for SIGMA 2002
Page 2: ......
Page 99: ...Blue Box 93 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 SIGMA 2002 DC MODELS 3 2 13 2...
Page 100: ...Blue Box 94 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 SIGMA 2002 DC MODELS 14 4 26 4...
Page 101: ...Blue Box 95 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 HP MODELS 3 2 8 2 14 4 16 4...
Page 102: ...Blue Box 96 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 HP MODELS 9 2 13 2 18 4 26 4...
Page 103: ...Blue Box 97 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LE SIGMA 2002 LE DC MODELS 3 2 26 4...
Page 104: ...Blue Box 98 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LE HP MODELS 3 2 26 4...
Page 105: ...Blue Box 99 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC MODELS 3 2 13 2...
Page 106: ...Blue Box 100 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC MODELS 14 4 26 4...
Page 107: ...Blue Box 101 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC HP MODELS 3 2 13 2...
Page 108: ...Blue Box 102 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC HP MODELS 14 4 26 4...
Page 109: ...Blue Box 103 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC DC MODELS 3 2 13 2...
Page 110: ...Blue Box 104 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC DC MODELS 14 4 26 4...
Page 123: ......