Models 14.4 - 26.4, controller pCO
2
Blue Box - Page 82
SYMPTOM
OPERATION
PROBABLE CAUSE
POSSIBLE CORRECTIVE ACTION
COOLING
HEATING
E3)
No compressor
running. Display On:
⊗
⊗
Insufficient percentage of
glycol in hydraulic circuit
Restore correct glycol percentage
unit ON with alarm
“Low Pressure
Compressor 1, 2, 3, 4”
⊗
⊗
Both circuits have
insufficient refrigerant
charge
Find possible leaks in circuit,
repair, and recharge
⊗
Incorrect setting of defrost
set-point (only version
LC/HP)
Check and correct setting if
necessary
E4)
No compressor
running. Display On:
unit ON with alarm
⊗
⊗
Insufficient water flow to
evaporator
Increase water flow to
evaporator and check
temperature rise
“Exceeded Threshold
Low Temperature of
leaving User Water”.
⊗
⊗
Faulty controller
Contact service organisation
E5)
No compressor
running. Display On:
unit ON with alarm
“Exceeded Threshold
High Temperature of
⊗
⊗
Excessive thermal load
Wait until entering water
temperature is below the alarm
set point. Start hydraulic circuit
of evaporator and unit. If not
sufficient contact assistance.
entering User Water
⊗
⊗
Refrigerant circuits partially
discharged
Call assistance
E6)
(Only version LC)
No compressor
running. Display On:
unit ON with alarm
“Fans protection”
⊗
⊗
Depending upon the fan
type installed
Check thermal consent of fans
Summary of Contents for SIGMA 2002
Page 2: ......
Page 99: ...Blue Box 93 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 SIGMA 2002 DC MODELS 3 2 13 2...
Page 100: ...Blue Box 94 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 SIGMA 2002 DC MODELS 14 4 26 4...
Page 101: ...Blue Box 95 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 HP MODELS 3 2 8 2 14 4 16 4...
Page 102: ...Blue Box 96 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 HP MODELS 9 2 13 2 18 4 26 4...
Page 103: ...Blue Box 97 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LE SIGMA 2002 LE DC MODELS 3 2 26 4...
Page 104: ...Blue Box 98 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LE HP MODELS 3 2 26 4...
Page 105: ...Blue Box 99 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC MODELS 3 2 13 2...
Page 106: ...Blue Box 100 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC MODELS 14 4 26 4...
Page 107: ...Blue Box 101 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC HP MODELS 3 2 13 2...
Page 108: ...Blue Box 102 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC HP MODELS 14 4 26 4...
Page 109: ...Blue Box 103 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC DC MODELS 3 2 13 2...
Page 110: ...Blue Box 104 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC DC MODELS 14 4 26 4...
Page 123: ......