Blue Box - 29
4.4 EVAPORATOR WATER PIPE CONNECTIONS
The water inlet and outlet must be connected in the positions indicated
as labelled on the unit.
A constant water flow to the evaporator must be guaranteed at all
operating conditions to prevent liquid refrigerant from entering the
compressor and causing irreparable damage.
Compressors start and stop often due to changes in cooling demand. In hydraulic circuits with low water volume,
where the thermal inertia action is low, it is advisable to verify that the water volume equals or exceeds the
following ratio:
24 · Q
COMPTOT
M>= ---------------------
N
where:
M
= system water content [kg]
Q
COMPTOT
= unit cooling capacity [kW]
N
= number of capacity steps
If the water volume does not reach the value given by the formula, it is advisable to provide the circuit with a
storage vessel to increase the volume (tank + circuit) to match the result of the formula.
The chilled water piping and storage vessel must be insulated to prevent condensation on the pipe surfaces and
to avoid circuit performance losses.
On all units it is compulsory to install a flow switch. If a flow switch is not
installed, on the evaporator leaving water connection, the warranty will
be terminated immediately.
The flow switch must be installed, by the
contractor, on the evaporator water outlet connection labelled with:
If incorrectly connected the antifreeze thermostat will not operate and the evaporator may freeze.
The hydraulic connections are threaded. The type and size are indicated on the dimensional drawings at the end
of this manual.
HEAT PUMP units require a second flow switch is provided with the unit.
This must be installed, by the contractor, on the condenser outlet
connection labelled with:
CONDENSER WATER
EVAPORATOR WATER
EVAPORATOR WATER
Summary of Contents for SIGMA 2002
Page 2: ......
Page 99: ...Blue Box 93 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 SIGMA 2002 DC MODELS 3 2 13 2...
Page 100: ...Blue Box 94 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 SIGMA 2002 DC MODELS 14 4 26 4...
Page 101: ...Blue Box 95 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 HP MODELS 3 2 8 2 14 4 16 4...
Page 102: ...Blue Box 96 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 HP MODELS 9 2 13 2 18 4 26 4...
Page 103: ...Blue Box 97 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LE SIGMA 2002 LE DC MODELS 3 2 26 4...
Page 104: ...Blue Box 98 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LE HP MODELS 3 2 26 4...
Page 105: ...Blue Box 99 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC MODELS 3 2 13 2...
Page 106: ...Blue Box 100 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC MODELS 14 4 26 4...
Page 107: ...Blue Box 101 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC HP MODELS 3 2 13 2...
Page 108: ...Blue Box 102 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC HP MODELS 14 4 26 4...
Page 109: ...Blue Box 103 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC DC MODELS 3 2 13 2...
Page 110: ...Blue Box 104 REFRIGERANT CIRCUIT DIAGRAM SIGMA 2002 LC DC MODELS 14 4 26 4...
Page 123: ......