Turning of the interval timer on and its adjustment is performed with the potentiometer Ti. To turn the interval timer
off set the potentiometer Ti into the leftmost position. Rotation of the potentiometer for 1/3 clockwise sets the interval
timer operation for 6 hours, rotation of the potentiometer for 2/3 clockwise sets the interval timer operation for 12 hours,
rotation of the potentiometer clockwise in the rightmost position sets the interval timer operation for 24 hours.
To adjust the fan turn-off delay time, turn the control knob
Toff
clockwise to increase and counter-clockwise to
decrease the turn-off delay time respectively, adjustable from 2 up to 30 minutes.
To adjust the humidity set point turn the control knob
H
clockwise to increase and counter-clockwise to decrease
the humidity sensor set point, adjustable from 60 % up to 90 %.
Warning!
The timer circuit is live!
Disconnect the fan from power supply prior to any adjustment operations.
The fan delivery set includes a specially designed plastic screwdriver for fan settings adjustments.
Use it to change the turn-off delay timer, interval timer settings or the humidity sensor set point.
Do not use a metal screwdriver, knife, etc. for adjustment operations not to damage the circuit board.
H
T
і
T
off
-
60%
90%
H
+
-
+
+
-
off
24
hour
T
і
+
-
2min
30min
T
off
For
Ò
For
Í
6
hour
12
hour
Summary of Contents for Sileo V2
Page 1: ...EN Sileo V2 OPERATION MANUAL ...
Page 11: ...11 6 10 7 4 11 8 5 12 9 6 QF L N ...
Page 17: ...17 24 25 22 23 20 21 QF L N Latches ...
Page 18: ...18 notes ...
Page 20: ...Sileo V2 Sileo V2 v1 1 EN ...