S30, S31, S32
16
www.blaubergventilatoren.de
ALARMS
In case of alarm the alarms are displayed on the display.
5
2
1
3
4
Position
Description
1
Alarm number / total alarms
2
Alarm date and time
3
Alarm code
4
Alarm description
5
Alarmed sensor value
The alarms can be reset manually, automatically or repeated automatically.
• Manual reset: after troubleshooting an alarm reset the audio signal using the ALARM button, then press and hold the
button
for 3 seconds for final reset.
• Automatic reset: after automatic troubleshooting of the alarm the audio signal turns off and the signal is reset.
• Automatically repeated reset: the system checks number of repeated interventions per hour. If this number is below the set
maximum value, the alarm is automatically reset. As soon as the limit is crossed, the alarm must be reset manually.
Alarm list
Alarm
code
Alarm description
Reset
Action
A000
Supply temperature sensor not working
Automatic reset
Unit shutdown
A001
Cooling device alarm
Reset by user
Cooler shutdown
A002
Antifreeze alarm by DIN
Automatic reset to counter (filter
timer) value (3 times 3600 s)
Unit shutdown and forced 100%
power heating
A003
Prototype software
Automatic reset
Unit shutdown
A004
High number of retain memory writings
Reset by user
No
A005
Error in retain memory writings
Reset by user
No
A006
Return temperature sensor broken not working
Automatic reset
Changeover in the supply control
mode
A007
External temperature sensor broken not working
Automatic reset
Deactivation of outdoor air
temperature compensation mode
A008
CO
2
air quality sensor not working
Automatic reset
Deactivation of CO
2
control mode
A009
Exhaust temperature sensor not working
Automatic reset
Unit shutdown
A010
th-Tune offline
Automatic reset
Deactivation of indoor air
temperature compensation mode
A011
Supply temperature out of range
Automatic reset
No
A012
Supply air flow alarm
Reset by user
Unit shutdown
A013
Return air flow alarm
Reset by user
Unit shutdown
A014
Humidifier alarm
Automatic reset
Humidifier shutdown
A015
Humidifier maintenance required
Automatic reset
No
A016
Return fan maintenance required
Automatic reset
No
A017
Supply fan maintenance required
Automatic reset
No
A018
Reheating coil maintenance required
Automatic reset
No
A019
Heat recovery maintenance required
Automatic reset
No