www.blaubergventilatoren.de

S30, S31, S32

15

5. Main temperature control (air temperature in the supply air duct). 
6. Set indoor air or supply duct temperature point (depending on settings).
7. Indicates access to the user menu with UP, DOWN and ENTER buttons. 
 

INFO:   indicates general condition of devices, operation status of outputs and inputs of devices and sensors. 

 

SET:  

indicates current set point and operation mode according to schedule. It is possible to set the set points 

 

         

for devices and schedule. 

 

MODE:   indicates changing of operation mode (stop, economy, precomfort, comfort, auto, in mask X00a).

8. Supply fan speed. 
9. Extract fan is on. 
10. Extract fan speed. 

Set-up of scheduled mode. 

Press ENTER to switch to menu in the SET mode. 
The menu has three set points: 
1) Setup of operation mode for each week day. It is possible to set maximum four time bands for one day (from Monday till Sunday) 
and start time for set mode. 

1

4

2

3

1: Selection of week day for setup. 
2: Copying of set parameters to enter for the other week day. Select Yes to copy parameters on the next day (parameter Copy to). 
3: Setting number of time bands for the day. Current mode exits as the next mode starts. 
4: Saving set parameters. 
2) Setting operation mode for 3 time bands (from one day till one year). 
Current operation mode exits as the next mode starts. 

3) It is possible to set a day for switching to set mode. 
It is possible to set maximum 6 days. Current operation mode exits as the next mode starts. 

To activate the schedule mode set the value I007 for the BOARD parameter in the section Unit cfq.

Summary of Contents for S30

Page 1: ...BLAUAIR AUTOMATIC CONTROL SYSTEM S30 KVENT TH TUNE S31 KVENT S32 KVENT PGDE USER S MANUAL EN ...

Page 2: ...tion systems and should be able to perform works in accordance with workplace safety rules as well as construction norms and standards applicable in the territory of the country The information in this user s manual is correct at the time of the document s preparation The Company reserves the right to modify the technical characteristics design or configuration of its products at any time in order...

Page 3: ...ith wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit Disconnect the unit from power mains prior to any technical maintenance SAFETY REQUIREMENTS Please read the user s manual carefully prior to installing and operating the unit All user s manual requirements as well as the provisions of all the appli...

Page 4: ...dually configured for each ventilation system The control panels are rated for non stop operation THE UNIT SHOULD NOT BE OPERATED BY CHILDREN OR PERSONS WITH REDUCED PHYSICAL MENTAL OR SENSORY CAPACITIES OR THOSE WITHOUT THE APPROPRIATE TRAINING THE UNIT MUST BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST...

Page 5: ... 90 no condensation Operation temperature C 10 60 20 60 Operation humidity 10 90 no condensation 10 90 no condensation Cable AWG 20 or AWG 22 up to 500 m Telephone cable max 50 m twisted pair AWG 22 max 500 m Ingress Protection IP20 IP40 Overall dimensions for thTune control panel Overall dimensions for pGDE control panel 86 8 22 5 28 86 48 82 31 11 64 156 135 ...

Page 6: ...side of the control panel 3 Complete the electric connection in compliance with wiring diagram 4 Fix the back side of the control panel in the mounting box using the supplied screws 5 Re connect the 4 pin connector 6 Lay all the wires inside of the control panel and install the control panel from the bottom Press the control panel front side to click to complete installation 4 5 6 4 5 6 Overall di...

Page 7: ... Lay the telephone cable to the installation place of the control panel 1 Fix the back side of the control panel inside of the mounting box using the supplied round head screws 2 Connect the telephone cable to the front side of the control panel Attach the front side of the control panel to its back side using the supplied countersunk head screws as shown below Press the control panel front side t...

Page 8: ...utomatic circuit breaker must exceed the maximum current consumption of the unit refer to the Technical data section The recommended trip current of the circuit breaker is the next current in the standard trip current row following the maximum current of the connected unit The automatic circuit breaker is not included in the delivery set and can be ordered separately DO NOT LAY THE VENTILATION UNI...

Page 9: ...larm panel 2x0 75 mm2 NC 2x0 75mm2 P1 External control panel thTUNE thTUNE 5x0 25mm2 PD1 Filter clogging sensor NC 2x0 75mm2 Not supplied with the unit Available as specially ordered accessories The unit may be supplied with the thTUNE control panel The wire cross section is valid for the max cable length 100 m Alarm signal is a digital output that changes its status in case of alarm ...

Page 10: ...laubergventilatoren de CONTROL Display port BMS Fieldbus2 BMS Field bus Fieldbus2 BMS configuration BMS Fieldbus1 BMS Display port Ethernet USB BMS card 1 12 5 13 14 6 7 10 11 8 9 2 3 4 S31 controller KVENT inputs outputs ...

Page 11: ...pecially ordered accessory 13 Jumpers for configuration of BMS Fieldbus2 port 14 Power input Ventilation unit control with a mobile device Display port BMS Control stand by Fieldbus2 BMS Fieldbus1 BMS Display port Ethernet USB Ethernet Internet LAN WAN The ventilation unit is controllable via a mobile device or tablet Connect the router through the Ethernet LAN connector using the twisted pair 4 x...

Page 12: ...9 DISPLAY SYMBOLS 1 System on off indication 2 Main field current indoor temperature field for temperature setup schedule setup etc 3 Operation modes ECO PECOMFORT COMFORT AUTO 4 Temperature measurement unit 5 Schedule blocking function the pictogram appears in case of attempt to activate schedule on unconfigured unit 6 Set value 7 Humidity measurement unit 8 Current time band 9 Day week 10 Coolin...

Page 13: ... ENCODER buttons to get access to the settings Then rotate ENCODER to select several days or one day to set an operation mode as follows 7 days mon tue wed thu fri sat sun For Monday Tuesday Wednesday Thursday Friday Saturday and Sunday the time band settings are common 5 days mon tue wed thu fri For Monday Tuesday Wednesday Thursday and Friday the time band settings are common 2 days sat sun For ...

Page 14: ...reset to parameter list UNIT START After connection of the unit to power mains the controller is loaded and the home page opens 5 6 7 2 1 8 9 10 3 4 1 Day and time 2 Supply fan is on 3 Operation mode STOP ECONOMY PRECOMFORT COMFORT AUTO 4 Current unit condition damper opening closing fan run heating cooling FC FH free heating cooling humidification dehumidification active heat recovery standard sh...

Page 15: ...ress ENTER to switch to menu in the SET mode The menu has three set points 1 Setup of operation mode for each week day It is possible to set maximum four time bands for one day from Monday till Sunday and start time for set mode 1 4 2 3 1 Selection of week day for setup 2 Copying of set parameters to enter for the other week day Select Yes to copy parameters on the next day parameter Copy to 3 Set...

Page 16: ...nter filter timer value 3 times 3600 s Unit shutdown and forced 100 power heating A003 Prototype software Automatic reset Unit shutdown A004 High number of retain memory writings Reset by user No A005 Error in retain memory writings Reset by user No A006 Return temperature sensor broken not working Automatic reset Changeover in the supply control mode A007 External temperature sensor broken not wo...

Page 17: ...arm Automatic reset Unit shutdown A036 Supply humidity sensor not working Automatic reset Humidifier shutdown A037 Unit configuration not allowed Automatic reset Unit shutdown A038 Supply fan Offline Automatic reset Unit shutdown A039 Supply fan Line Fault Automatic reset Unit shutdown A040 Supply fan Motor blocked Automatic reset Unit shutdown A041 Supply fan Fire alarm Automatic reset Unit shutd...

Page 18: ...rn fan Hall sensor error Reset by user Unit shutdown A089 Return fan Offline Reset by user Unit shutdown A090 Return fan Phase failure Reset by user Unit shutdown A091 Return fan Motor blocked Reset by user Unit shutdown A092 Return fan Mains undervoltage Reset by user Unit shutdown A093 Return fan Mains overvoltage Reset by user Unit shutdown A094 Return fan DC link overvoltage Reset by user Unit...

Page 19: ...evice 2 maintenance required Automatic reset No A422 Out of design temperature limits alarm Automatic reset Opening air mixing unit or ventilation shutdown if mixing unit is not available A429 Heat exchanger clogged Automatic reset Shutdown of heat recovery A430 Door switch Automatic reset Unit shutdown THE ENGINEERING SETTINGS ARE PASSWORD PROTECTED FOR DETAILED DESCRIPTION OF ENGINEERING SETTING...