Servicing of the unit is required 3-4 times per year. 
Disconnect the unit from power mains prior to any maintenance operations. 

The unit maintenance includes regular cleaning of the unit surfaces and 

components from dust and filter cleaning or replacement. 
To remove dust in the air handling unit use a soft brush, a cloth or compressed 

air. Do not use water, abrasive detergents, sharp objects and solvents. Clean the 

impeller blades once a year.
Soiled filters increase air resistance and decrease the unit performance. The 

filters can be cleaned with a vacuum cleaner or with running water. Let the 

filters dry well at least for 24 hours. The filters require cleaning at least 3-4 times 

per year. 
For accessing the unit filters open the front panel, fig. 1. 
Regular cleaning is required to maintain the high heat recovery efficiency of the 

heat exchanger. To clean the heat exchanger use a vacuum cleaner or flush it 

under running water. And at least 24h to dry well.

MAINTENANCE

Fig. 13. SGR-3/1 sensor speed switch mounting 

Mounting sequence of the sensor speed switch, fig. 13: 

1. Carefully undo the latches of the switch front panel with a screwdriver.  

2. Remove the front panel. 

3. Route the cable to the installation place of the speed switch. 

4. Fix the back panel to the wall through the fixing holes. 

5. Connect the control cable to the speed switch following the wiring 

diagram, fig. 12. 

6. Install the speed switch front panel on the latches. 

TROUBLESHOOTING

Fault

Possible reasons

Remedy

The fan does not start when the unit 

is on.

No power supply.

Make sure of correct power supply, otherwise troubleshoot the connection 

error. 

Cold supply air.

Extract filter is clogged.

Clean or replace the extract filter.

The heat exchanger is frosted. 

Check the heat exchanger for frosting. Shut the unit off if required and let 

ice melt. 

Low air flow.

The filters, the fans or the heat exchanger are 

soiled. 

Clean or replace the filters; clean the fans and the heat exchanger.

The air ducts or the outer hood are soiled or 

mechanically damaged.

Clean or replace the damaged air ducts or the outer hood.

Noise, vibration.

The impeller blades are clogged. 

Clean the impeller blades.

Loose screw connection.

Tighten the fastening screws.

Table 2. Error list and troubleshooting

Summary of Contents for FRESHBOX 60

Page 1: ...OPERATION MANUAL FRESHBOX 60 SINGLE ROOM AIR HANDLING UNIT WITH HEAT RECOVERY ...

Page 2: ...ansportation rules 3 Manufacturer s warranty 3 Unit design and operating logic 4 Delivery set 4 Technical data 5 Mounting and operation guidelines 5 Connection to power mains and control 8 Maintenance 9 Troubleshooting 9 Acceptance certificate 10 Connection certificate 10 Warranty card 10 CONTENTS ...

Page 3: ...ection Technical data Do not close or block the unit intake or exhaust vent not to disturb the normal air passage Do not sit on the unit and do not put objects on the unit Follow the manual guidelines to ensure trouble free operation and long service life of the product Hazardous parts access and water ingress protection standard IP22 STORAGE AND TRANSPORTATION RULES Transportation of the unit is ...

Page 4: ...g efficiency reaches 79 The air flows are fully separated within the heat exchanger Odours and con taminants contained in the extract air are not transferred to the supply air flow Heat recovery is based on the utilization of the thermal energy of the ex tract air for heating up the supply air The extract air transfers most of its heat to the intake air flow This reduces thermal energy losses in c...

Page 5: ... construction stage It includes two plastic air ducts each 500 mm long and two master plates for marking the holes on inner and outer wall sides The mounting set MS2 FRESHBOX 60 is specially designed for mounting of the unit in a ready built premise It includes two plastic air ducts 500 mm long a master plate for matching holes and an outer ventilation hood AH FRESHBOX 60 that prevents ingress of ...

Page 6: ... the solidification time in the product specification remove the master plates At the inner wall cut the protruding parts of the air ducts to be flush with the wall On outer wall side the air ducts must protrude by 10 mm to prevent condensate dropping on the wall 7 Mounting sequence of the unit a take off the front cover and remove the heat exchanger fig 8 b connect the unit spigots to the air duc...

Page 7: ... mounting set includes plastic air duct Ø 125 mm 500 mm long 2 items paper master plate 1 item outer ventilation box AH FRESHBOX 60 1 item screw and dowel 8x40 4 items Mounting sequence of MS2 FRESHBOX 60 set 1 Fix the master plate from the delivery set on inner wall side with a sealing tape on required level fig 5 2 Use the master plate to mark two Ø 140 mm holes for the air ducts and two Ø 8 mm ...

Page 8: ...uch a respective speed button to change the selected speed The respective speed button has blue highlighting Touch a current fan speed button once again to turn the air handling unit off The sensor panel has no light indication when the unit is off Every time the sensor panel is touched a sound signal is generated The control unit is installed under the protecting panel of the air handling unit fi...

Page 9: ...peed switch mounting Mounting sequence of the sensor speed switch fig 13 1 Carefully undo the latches of the switch front panel with a screwdriver 2 Remove the front panel 3 Route the cable to the installation place of the speed switch 4 Fix the back panel to the wall through the fixing holes 5 Connect the control cable to the speed switch following the wiring diagram fig 12 6 Install the speed sw...

Page 10: ...rective 2006 95 EC 73 23 EEC and CE marking Directive 93 68 EEC on the approximation of the laws of the Member States relating to electromagnetic compatibility This certificate is issued following test carried out on samples of the product referred to above Approval mark Manufacturing date____________________ The single room air handling unit with heat recovery FRESHBOX 60 is connected to power ma...

Page 11: ..._______________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ ________________...

Page 12: ...www blaubergventilatoren de FRESHBOX 60 v 5 3 EN ...

Reviews: