ADDITIONAL SCALING PAOAMETEOS
OTEE:
N
The programming instructions below are only available for loop powered units Battery powered units do not include
these programming parameters
Flow 4 mA Setting
Zero is the default flow rate at the 4 mA setting If the current selection is correct, press
ENTEO
to advance to the
Flow 20 mA
parameter To change the setting, press
UP
to increment the flashing digit and press
OIGHT
to move to the next digit Press
ENTEO
to save and advance to the
Flow 20 mA
parameter
Flow 20 mA Setting
The turbine meter’s maximum flow rate is the default value for the 20 mA setting If the current selection is correct, press
ENTEO
to advance to the
4…20 mA Calibration
parameter To change the setting, press
UP
to increment the flashing digit and
press
OIGHT
to move to the next digit Press
ENTEO
to save and advance to the
4…20 mA Calibration
parameter
4…20 mA Calibration
The
4…20 mA Calibration
parameter is the fine adjustment of the 4…20 mA output The 4 mA setting is typically between
35…50 To set the 4 mA value, connect an ammeter in series with the loop power supply At the
4MA OUT
prompt, press
UP
to
increment and
OIGHT
to decrement the 4 mA value to until a steady 4 mA reading is reached on the ammeter Press
ENTEO
to
lock in this value and advance to
20MA OUT
The 20 mA adjustment is performed using the same procedure as the
4 mA adjustment
4…20 mA Test
The monitor contains a diagnostic routine that allows the simulation of mA values between 4…20 to check output tracking
At the
4-20TEST
prompt press
UP
to increment the simulated mA output or
OIGHT
to decrement the value in increments of
1 mA The ammeter should track the simulated mA output If a 4…20 mA test in not necessary, press
ENTEO
once to escape
the testing at any time
Pulse Out
Freq. In
4-20 mA
10…30V DC
1…5V DC
1
2
3
4
5
6
+ -
+ -
+ -
JP2
Mag
Input
Pulse
Inuput
TB1
1 2 3 4 5
J2
Keypad
Connector
DC
PULSE OUTPUT
IO/SETUP
DSP
Flow 4MA
Flow 20MA
4MA OUT
20MA OUT
4-20 TEST
PASSWORD
Figure 4: Typical ammeter connection
Figure 5: 4…20 mA programming menu
Additional Scaling Parameters
Page 8
March 2017
DSY-PM-00278-EN-03