Blagdon Powersafe Series Quick Start Manual Download Page 5

1.  

Prepare the cable (see cable preparation diagram - inside front cover). 

  A maximum external cable diameter of 9mm is permitted.

2.  

Remove the cable gland cover and thread it over the cable of the appliance to be fitted.  

  (see gland detail diagram on colour Switch box wiring diagram - inside front cover).

Note: The cable glands have a plug that should be retained if the gland is not being 
used for a application. This should be inserted to maintain a weatherproof seal.

INSTALLATION

5

IMPORTANT: 

Please note that the mains input must be connected to the green power input 

cable block only.

 

Switch one has a maximum loading of 1000w 1.0KW.

 

Switch two and subsequent switches are rated to a maximum wattage of 300w 0.3 KW.

 

These ratings must not be exceeded by the maximum wattage stated on the appliance to be 

fitted to each switch.

Circuit Board Removal

Remove the circuit board by 
unscrewing the locating screw 
and wire each appliance 
before replacing and locating 
into the box.

Summary of Contents for Powersafe Series

Page 1: ...e due to a blown fuse Each switch has an individual fuse to provide overload protection ensuring that even if one or more items of equipment fail the other essential equipment is still able to functio...

Page 2: ...LIGHT Switch on or off Fuse has blown no power Individual switch power outlets Power Supply Status TECHNICAL SPECIFICATION CHART SWITCH BOX 2 WAY 3 WAY 4 WAY 5 WAY Voltage 220 240V 220 240V 220 240V 2...

Page 3: ...current not exceeding 30mA must be installed in the supply circuit This unit should be connected to a mains supply that is fused with a 13 amp fuse or 15 amp circuit breaker IMPORTANT Do not drill or...

Page 4: ...s Failure to comply is a criminal offence If the installation of this product is not carried out by a competent electrician who is registered under the Part P self certification scheme then you must n...

Page 5: ...d for a application This should be inserted to maintain a weatherproof seal INSTALLATION 5 IMPORTANT Please note that the mains input must be connected to the green power input cable block only Switch...

Page 6: ...cable gland see cable gland sealing diagram 12 Screw and hand tighten the cable gland cover that was previously threaded onto the cable to the cable gland Now repeat this process for all the applianc...

Page 7: ...lifting in a vertical action 2 Remove the four cover locating screws from the back of the box 3 Having identified which switch fuse has blown 5 amp for switch 1 or 1 5 amp for subsequent switches rem...

Page 8: ...atergardening co uk www pondaquariumproblemsolver co uk blagdon IMPORTANT 8 GUARANTEE This product is guaranteed against defects in material and workmanship for 3 years from the date of purchase under...