background image

NOTICE:

THIS PUMP CONTAINS SOME RESIDUAL TEST FLUID
AND RUST INHIBITOR.  IF NECESSARY, FLUSH PUMP
PRIOR TO USE.

Hazardous voltage.
Can shock, burn 
or cause death.

Install, ground and wire to local and
National Electrical Code requirements.

Install an all-leg disconnect switch near
the unit motor.

Disconnect and lockout electrical power
before installation or service.

Electrical supply MUST match motor nameplate
specifications.

Motors equipped with thermal protection automatically
disconnect motor electrical circuit when overload exists.
Motor can start unexpectedly and without warning.

NOTICE:

BLACKMER CO2 PUMPS MUST ONLY BE INSTALLED
IN SYSTEMS DESIGNED BY QUALIFIED ENGINEERING
PERSONNEL.  SYSTEM DESIGN MUST CONFORM
WITH ALL APPLICABLE REGULATIONS AND CODES
AND PROVIDE WARNING OF ALL SYSTEM HAZARDS.

INSTALLATION AND OPERATION 

CRL BASE MOUNTED MOTOR DRIVEN PUMPS

PRE-INSTALLATION CLEANING

Foreign matter entering the pump WILL cause extensive
damage.  The supply tank and intake piping MUST be cleaned
and flushed prior to pump installation and operation.

LOCATION AND PIPING

An improperly designed piping system or improper unit
installation WILL significantly reduce pump performance and
life.  Blackmer recommends the following piping system layout
and unit installation.  See Figure 2.
1. To minimize intake losses, locate the pump as close as

possible to the source of supply and a minimum of two
feet (0.6 m) below the tank outlet.

2. Intake piping and fittings MUST be at least as large in

diameter as the pump intake connection.  Inlet piping must
be insulated.

3. Use high strength Schedule “80” piping.
4. Minimize the number of intake line fittings (valves, elbows,

etc.) and piping turns or bends.  The nearest fitting on the
intake line must be at least 6 inches (152 mm) from the
pump to permit access to the pump relief valve .

5. Install an intake strainer 5 - 10 pipe diameters from the

pump intake.  The strainer must have a net open area of at

least four times the area of the intake pipe.  Strainers must
be cleaned regularly to avoid pump starvation.

6. Intake and discharge piping MUST be free of all leaks.

7. To facilitate piping expansion and contraction, expansion

joints must be placed 3 feet (0.9 m) from the pump intake
and discharge.

8. ALL piping and fittings MUST be properly supported to

prevent any piping loads from being placed on the pump.

9. Install pressure gauges in the NPT ports provided in the

pump casing to check pump performance at start up.

10. The use a vapor return line will speed up delivery by

preventing back pressure from building up at the receiving
tank and reducing pressure in the supply tank.

11. Keeping the liquefied gas systems full of liquid, even when

idle, will keep the O-rings from changing shape, shrinking
or super cooling.  Evaporation of liquefied gas leaves an
abrasive powder on the surface which can cause wear to
the pump, meter, and seals.

PUMP MOUNTING

Permanently mount the unit by securing the base plate with
adequately sized anchor bolts to a level concrete floor
following recommended
industry standards (See
Figure 3).  A solid foundation
will reduce system noise and
vibration, and will improve
pump performance.  Refer to
ANSI/HI standards or a
suitable pump handbook for
information on typical pump
mounting and foundations.
Check coupling alignment
after pump and base
assembly is secured to the
foundation.

BOLT

BASE

STANDARD

PIPE

WASHER

Figure 3

BOLT

BASE

STANDARD

PIPE

WASHER

COUPLING ALIGNMENT

The pump must be directly coupled to a gear, gear reducer,
and/or driver with a flexible coupling.

Both angular and parallel coupling alignment MUST be
maintained between the pump, gear reducer, motor, etc. in
accordance with manufacturer’s instructions.  See Figure 4.

1. To check for parallel alignment, the use of a dial indicator is

preferred.  If a dial indicator is not available use a straight
edge.  Turn both shafts by hand, checking the reading
through one complete revolution.  Maximum offset must be
less than .005" (125 microns).

2. To check for angular alignment, insert a feeler gauge

between the coupling halves.  Check the spacing in 90
degree increments around the coupling (four check points).
Maximum variation must not exceed .005" (125 microns).

Figure 4 - Alignment Check

3

Storage Tank

Figure 2

Unions

Bypass Valve

Gate or Ball
Valves

Intake Connection
for unloading tank
cars or tank trucks

Do no start
pump unless
this valve is
open.

Alternate
Discharge
to Storage
Tank

Discharge

Strainer

Summary of Contents for CRL4

Page 1: ...s which have been designed by qualified engineering personnel The system MUST conform to all applicable local and national regulations and safety standards This manual is intended to assist in the ins...

Page 2: ...ifferential Pressure INITIAL START UP INFORMATION TECHNICAL DATA PUMP WITH WELDED CONNECTIONS NOTICE FOR PIPING CONNECTIONS REQUIRING WELDING THE PUMP S NON METALLIC O RINGS MUST BE REMOVED PRIOR TO W...

Page 3: ...tate piping expansion and contraction expansion joints must be placed 3 feet 0 9 m from the pump intake and discharge 8 ALL piping and fittings MUST be properly supported to prevent any piping loads f...

Page 4: ...the sheave capscrews 152C 152G the motor mounting nuts 184 and the adjusting screw locknut 183B 8 Assemble the belt guard 182 and the belt guard brace 182A to the unit base 32 9 Check the belt tension...

Page 5: ...rating pressure or the system pressure control valve setting Refer to Relief Valve Setting and Adjustment section of this manual 8 The external bypass valve must always be set at least 25 psi 1 7 bar...

Page 6: ...e off through universal joints When using universal joints a splined slip joint properly lubricated must be used on the connecting jack shaft to prevent end thrust on the pump shaft It is very importa...

Page 7: ...over the non driven shaft end a Lever Operated Pull the control knob all the way out Manually check the lever under the truck to see that it is in the completely OPEN position b Discharge Pressure Op...

Page 8: ...or the system pressure control valve setting Relief Valve Adjustment Procedure 1 To INCREASE the pressure setting remove the relief valve cap 1 loosen the locknut 3 and turn the adjusting screw 2 inw...

Page 9: ...Slide the head 20 off the shaft The head O ring 72 disc 71 bearing 24 and mechanical seal 153 will come off with the head assembly Remove and discard the head O ring a Remove the four disc machine sc...

Page 10: ...th the rounded edges outward and the vane relief grooves facing TOWARDS the direction of rotation Refer to Figure 7 d After the bottom vanes 14 and push rods 77 are installed carefully insert the roto...

Page 11: ...the aligned lockwasher tang into the slot in the locknut The pump must continue to turn freely when rotated by hand g To check adjustment grasp the locknut 24A and lockcollar 24B with fingers and rota...

Page 12: ...damaged 7 Vibration from improperly anchored piping 8 Bent shaft or drive coupling misaligned 9 Excessively worn rotor 10 Malfunctioning valve in the system 11 Relief valve setting too low 12 Liner in...

Reviews: