35
LOAD
+
-
RS-485
RS-485
RS-485
Power Line
Power Line
After wiring is complete, configure one of the supplies as the Master and the
other three as Slave A, B, and C. After one of the supplies is configured to be
the Master, it will start searching for all Slaves that are connected to the Master.
To operate correctly, the user must set up the Slaves before the Master.
To set a supply to slave mode, press
,
,
and
in the main
screen to enter the PARALLEL SETTING option. Then select the parallel
mode by turning the knob and then press
to confirm. It will continue
to the next line for the MASTER/SLAVE selection. Turn the knob to select
SLAVE A for the supply and press
to confirm the setting. Using the
same procedure, set up SLAVE B and C for two other supplies as shown below.
To set the master unit, press
,
, and
in the main screen
to enter the PARALLEL SETTING option. Then use the knob to select the
parallel mode and press
to confirm. It will continue to the next line for
the MASTER/SLAVE selection. Use knob again to select MASTER and then
press
to confirm. Once the supply is confirmed as the Master supply,
it will start searching for all other Slaves connected, as shown below:
L
=
= L
FF