Opto-electronical  
Oil Level Monitoring   
for CS. Compressors 

• OLC-D1-S 

1 Application 

An adequate oil supply is very important 
for the operating life of a compressor. 
Lack of lubrication, e. g. due to oil short 
age. Even a short interruption of the oil 
supply can destroy the roller bearings. 

The OLC-D1-S is an opto-electronical 
sensor for contactless monitoring of the 
oil level by means of infrared light. 

Depending on the mounting position and 
electrical connection, the same device 
can be used for monitoring the minimum 
and maximum oil levels. 

The monitoring device consists of two 
parts: a prism unit and an opto-electronic 
unit. 

•  The prism unit is mounted directly into 

the compressor housing. 

•  The opto-electronic unit is not in direct 

contact with the refrigerant circuit. It is 
screwed into the prism unit and 
integrated into the control circuit of the 
plant. An external control module is 
not required. 

CS. 

コンプレッサー用

 

光学式オイルレベルモニター

 

 

• OLC-D1-S 

用途

 

コンプレッサーを運転する上で、適切な
オイル供給が非常に重要となります。オ
イル切れなどでたとえ短時間でも潤滑油
が不足すると、温度が急上昇してしまう
からです。また短時間でもオイル供給が
中断すると、ローラーベアリングが焼き
付きます。

 

OLC-D1-S

は赤外光利用の非接触光学式

オイルレベルモニターです。

 

取付け位置と電気的接続を変えること
で、同じ装置を最小

/

最大いずれのオイル

レベル監視にも使用できます。

 

モニター装置を構成する部品は、プリズム
ユニットと光学式ユニットの

2

つです。

 

• 

プリズムユニットはコンプレッサー
ハウジングに直付けします。

 

• 

光学式ユニットは冷媒回路とは直接
接触しません。プリズムユニットにネ
ジ止めされ、プラントの制御回路に統
合されます。外部制御モジュールは必
要ありません。

 

 

Summary of Contents for OLC-D1-S

Page 1: ...ntactless monitoring of the oil level by means of infrared light Depending on the mounting position and electrical connection the same device can be used for monitoring the minimum and maximum oil lev...

Page 2: ...lly The control voltage to the compressor contactor is interrupted The red LED at the face side of the opto electronic unit lights up figure 1 as well as the signal lamp H4 Reset The circuit can be ma...

Page 3: ...lektronische Einheit wird als OLC D1 ausgeliefert siehe Seite 2 Abbildung 1 Position 4 andere Spannungen auf Anfrage auch mit UL Abnahme erh ltlich Kabel sind farbkodiert 5 x AWG 20 0 75 mm2 L 2 m HFK...

Page 4: ...tch board Alternatively the OLC D1 S can also be used in combination with the optional protection device SE C1 for schematic wiring diagram please refer to next page 3 OLC D1 S SH 170 S4 OLC D1 S SE C...

Page 5: ...lectronical oil level monitoring SE E1 Compressor protection device standard SE C1 compressor protection device with extended functions option Maximum oil level monitoring To monitor the maximum oil l...

Page 6: ...In the standard scope of delivery this position is sealed with a plug Monitoring of the maximum oil level Mounting position See position 4 in figure 2 This is the position of the sight glass in the s...

Page 7: ...s l l nger als eine halbe Stunde der Atmos ph re ausgesetzt war die gleiche Menge neuen ls der selben lsorte einf llen 4 1 Mounting the prism unit Mount the OLC D1 S best before the compressor is inst...

Page 8: ...erstellen dass der Kabelanschluss immer nach unten weist Das OLC D1 S verriegelt wenn die opto elektronische Einheit nicht montiert ist 4 2 Mounting the opto electronic unit Slide the opto electronic...

Page 9: ...f monitoring device for maximum level Unscrew cap of opto electronic unit and remove opto electronic unit screwing cap see figure 1 The oil level is dispalyed behind the glass cone of the prism unit T...

Page 10: ...10 ST 130 2 Notes...

Page 11: ...ST 130 2 11 Notes...

Page 12: ...560 0082 1 4 2 14F TEL 06 6873 8555 FAX 06 6873 8556 www bitzer jp info bitzer jp Subject to change nderungen vorbehalten 80311102 01 2011...

Reviews: