v. 3.0
Reference guide
Compressor Control Module CM-RC-01
3.0
32 / 44
10.3.2
Status
– alarm
The group contains information about current state of alarms.
Modbus
type & addr
Name
Possible
values
Default
Description
IR 11100 Number of active
alarms
(AlarmStatus.Count)
unit None
scale 1
uint16
-
Number of active alarms
IR 11101 Number of listed
alarms that has not yet
been cleared
(AlarmStatus.CountList)
unit None
scale 1
uint16
-
Number of listed alarms that has not yet been
cleared
IR 11102 Highest state of any
listed alarm
(AlarmStatus.State)
unit None
scale 1
uint8
-
Highest state of any listed alarm
(0=Clear, 1=Inactive, 2=Active, 3=Set)
IR 11103 Highest severity level
of any active alarm
(AlarmStatus.Severity)
unit None
scale 1
uint8
-
Highest severity level of any active alarm
(0=None, 1=Log, 2=Event, 4=Info, 8=Warning,
16=Critical, 32=Fault)
IR 11104 If locked, ICP is waiting
for external reset
command or restart
(AlarmStatus.Locked)
unit None
scale 1
uint8
-
If locked, ICP is waiting for external reset
command or restart
(0=No, 1=Yes)
IR 11105 Reset level required to
clear any active alarm
(AlarmStatus.ResetLevel)
unit None
scale 1
uint8
-
Reset level required to clear any active alarm
(0=NA, 1=Auto, 2=Timer, 3=Extern, 4=Restart)
IR 11201 Code of highest ranked
alarm
(AlarmStatus.Alarm1)
unit None
scale 1
uint16
-
Code of highest ranked alarm
IR 11202 Code of second highest
ranked alarm
(AlarmStatus.Alarm2)
unit None
scale 1
uint16
-
Code of second highest ranked alarm
IR 11203 AlarmStatus.Alarm3
(AlarmStatus.Alarm3)
unit None
scale 1
uint16
-
IR 11204 AlarmStatus.Alarm4
(AlarmStatus.Alarm4)
unit None
scale 1
uint16
-
IR 11205 AlarmStatus.Alarm5
(AlarmStatus.Alarm5)
unit None
scale 1
uint16
-
IR 11206 AlarmStatus.Alarm6
(AlarmStatus.Alarm6)
unit None
scale 1
uint16
-
IR 11207 AlarmStatus.Alarm7
(AlarmStatus.Alarm7)
unit None
scale 1
uint16
-
IR 11208 AlarmStatus.Alarm8
(AlarmStatus.Alarm8)
unit None
scale 1
uint16
-
IR 11209 AlarmStatus.Alarm9
(AlarmStatus.Alarm9)
unit None
scale 1
uint16
-