Page 16
7.6. Modbus sample communica-
tion
Note: The following sample is a general Modbus commu-
nication sample and is not for the LMC341 DIWE!
Request: 0b041000000e75a4
Response: 0b041cffff0000095008b0e4a-
80014000b000108e108f1ffff000f0002fff39f8e
Request
0b03200000018f60
Response: 0b030200002045
8. Standards
The product is manufactured according to the following
standards.
RoHS 2002/95/EC
Low voltage 206/95/EC
EMC 2004/108/EC
61000-6-x Generic EMC
The following standards have been used:
EN 61010-1
Safety requirement for electrical equipment for
measurement and control.
EN 61000-6-2
Immunity standard for industrial environments.
EN 61000-6-3
Emission standard for residential, commercial and
lightindustrial environments.
CE approved.
Request (Input register)
0x0b
Slave address
1 byte
0x04
Function code
1 byte
0x1000
Start addr
2 bytes
0x000e
Quantity
2 bytes
0x75a4
CRC
2 bytes
Response
0x0b
Address
1 byte
0x04
Function code
1 byte
0x1c
NB bytes of data
1 byte
0xffff
Value1
2 bytes
0x0000
Value2
2 bytes
0x0950
Value3
2 bytes
0x08b0
Value4
2 bytes
0xe4a8
Value5
2 bytes
0x0014
Value6
2 bytes
0x000b
Value7
2 bytes
0x0001
Value8
2 bytes
0x08e1
Value9
2 bytes
0x08f1
Value10
2 bytes
0xffff
Value11
2 bytes
0x000f
Value12
2 bytes
0x0002
Value13
2 bytes
0xfff3
Value14
2 bytes
0x9f8e
CRC
2 bytes
Request (Holding register)
0x0b
Slave address
1 byte
0x03
Function code
1 byte
0x2000
Address
2 bytes
0x0001
Quantity
2 bytes
0x8f60
CRC
2 bytes
Reponse
0x0b
Slave address
1 byte
0x03
Function code
1 byte
0x02
Quantity
1 byte
0x0000
Value1
2 bytes
0x2045
CRC
2 bytes