Page 12
7.3. Outputs
Status of relay outputs.
Name
Possible
Values
Default
Description
Register
type
Address
Oil_Sensor
Unit Boolean
Scale 1
uint8
-
Oil level failure
(Input.Oil_Switch)
0: Off
1: Active
Input register
1566
SE-B1
Unit Boolean
Scale 1
uint8
-
Compressor overheated
(Input.Cpr_OH)
0: Ok
1: Failure
Input register
1567
Fan1_Fault
Unit Boolean
Scale 1
uint8
-
Fan1 failure
(Input.Fan1_OH)
0: Ok
1: Failure
Input register
1568
Fan2_Fault
Unit Boolean
Scale 1
uint8
-
Fan2 failure
(Input.Fan2_OH)
0: Ok
1: Failure
Input register
1569
DigIn1
Unit Boolean
Scale 1
uint8
-
Digital input 1
(Input.DigIn1)
0: Off
1: Active
Input register
1570
DigIn2
Unit Boolean
Scale 1
uint8
-
Digital input 2
(Input.DigIn2)
0: Off
1: Active
Input register
1571
ExtOnOff
Unit Boolean
Scale 1
uint8
-
External release input
(Input.ExtOnOff)
0: Off
1: Active
Input register
1572
SC_Cpr1
Unit Boolean
Scale 1
uint8
-
Security chain for compressor 1
(Only valid in dual compressor mode)
(Input.SC_Cpr1)
0: Ok
1: Failure
Input register
1573
SC_Cpr2
Unit Boolean
Scale 1
uint8
-
Security chain for compressor 2
(Only valid in dual compressor mode)
(Input.SC_Cpr2)
0: Ok
1: Failure
Input register
1574
Name
Possible
Values
Default
Description
Register
type
Address
RE1
Unit Boolean
Scale 1
uint8
-
Contactor K1 for frequency inverter /compressor
(Output.RE1)
0: Off
1: On
Input register
1584
RE2
Unit Boolean
Scale 1
uint8
-
Liquid Line Valve / Oil Return signal
(Output.RE2)
0: Off
1: On
Input register
1585
RE3
Unit Boolean
Scale 1
uint8
-
Crankcase heater
(Output.RE3)
0: Off
1: On
Input register
1586
RE4
Unit Boolean
Scale 1
uint8
-
Power for ΔpII and SE-B1
(Output.RE4)
0: Off
1: On
Input register
1587
RE5
Unit Boolean
Scale 1
uint8
-
Alarm relay
(Output.RE5)
0: Off
1: On
Input register
1588
RE6
Unit Boolean
Scale 1
uint8
-
RI (Refrigerant Injection)
(Output.RE6)
0: Off
1: On
Input register
1589