ACMI Operation Manual
11
Figure
4
Voltage DB-15 Power/Alarm Connector, Female
Pin
Description
1
Relay 1, VSWR alarm contact, normally closed
(closed when relay is not energized or loss of power to unit)
(open when the relay is engaged)
2
Relay 1, VSWR alarm common contact
3
Alarm output, TTL compatible
TTL High (
4.3 VDC with a 10k load) = no alarm
TTL Low (<0.2 VDC) = alarm (VSWR, Low, or High Power)
4
PTT input, +5V to +24V to activate,
0V or open to deactivate
5
Reset input, TTL compatible
TTL Low (<0.5 VDC) resets all active alarms
6
Relay 2, Power Alarm contact, normally closed
(closed when relay is not energized or loss of power to unit)
(open when relay is energized)
7
Relay 2, Power Alarm common contact
8
Relay 2, Power Alarm contact, normally open
(open when relay is not energized or loss of power to unit)
(closed when the relay is energized)
9
Relay 1, VSWR Alarm contact, normally open
(open when relay is not energized or loss of power to unit)
(closed when the relay is energized)
10
DC input, + terminal. See
11
DC input, – terminal. See
12
Analog FWD, 0 to 5 VDC linearly proportional to forward power, 200
ohm output impedance
13
Analog RFL, 0 to 5 VDC linearly proportional to reflected power, 200
ohm output impedance
14 - 15
Ground
Figure
5
Power/Alarm Connector Wiring, Female