Bircher Reglomat SWiSSDOOR ESR-3 Series Translation Of The Original Instructions Download Page 4

4





 



 





































Trouble Shooting

Initial Position:

– Connections according to wiring diagram

– Interrupt the power supply to the unit for a few seconds

a)  Start up test commences

No

Check the power supply at terminals 2/10 of socket. If the voltage is 

correct return the unit for servicing.

Yes

b) Press the “Reset” button. Does the start test function?

No

Return the unit for servicing

Yes

c) Do the yellow LED’s illuminate constantly?

Yes

Is a sensor activated?

Remove unit from socket 

Check the resistance at terminals 5/8 and 7/9 (7.5 to 9.0 kOhm)

No

d) Does the red LED “System Error” and “Unit Error” illuminate?

Yes 

Is the sensor wiring disconnected? Remove unit from socket 

Check the resistance at terminals (7.5 to 9.0 kOhm)

No

e) Is red LED “Unit Error” illuminated?

Yes

Return unit for service

No

Repeat the commissioning procedure.

1. The warranty and liability of Bircher Reglomat AG are based on the sales contract.
2. The warranty and liability shall expire prematurely, should the client or third parties not use 

and/or operate the product in compliance with existing operating instructions, should incorrect 
changes or repairs be made by the client or third parties, should the client or third parties, when 
a fault has occurred, not take suitable steps at once for a reduction of possible damage/losses 
and offer Bircher Reglomat AG a chance for remedying the said fault.

3. The warranty and liability shall exclude any damage for which there is no proof that it is due to 

poor materials, faulty construction, poor workmanship, and any damage caused by other rea-
sons, for which Bircher Reglomat AG cannot be held liable.

4.  No liability can be assumed for any consequential damage, provided this is not governed other-

wise by appli cable product liability laws and regulations.

5. Warranty claims made against the seller on the basis of the sales agreement are not affected 

by these regu lations.

6. For the benefit of its customers Bircher Reglomat AG constantly develops its products further. 

Bircher Reglomat AG reserves the right to make changes to any of the products described in this 
document without prior notice.

Identification of the year of manufacture

Contact

EC-Declaration of Conformity

Bircher Reglomat AG

Wiesengasse 20

CH-8222 Beringen

www.bircher-reglomat.com

Warranty and liability

Year   Month  Day

2015  06 

12

Test Phase Sequence after Connection of Voltage Operation

1s

1s

1s

1s

Operation

Housing

Type M3, material orange Noryl

Protection Class

IP 30 (IEC 529)

Weight

Max. 250 g (depending on type)

Supply Voltage

DC voltages are for battery power only

24 VDC +/-15%

24 VAC +/-15%

110 VAC +10/-15%

230 VAC +10/-15%

Frequency Range

50/60 Hz (45–66 Hz)

Power Consumption

max. 5 VA

Duty Cycle

100% 

Sensor Inputs

max. allowable voltage 15 VDC

max. allowable current 5 mA

Signal Output Relay

– Switching Capacity

2 A/250 VAC 1(ohm)

– Contact Material

Hard silver

– Operating Life

Mechanical 50 million switchings

Electrical 80’000 switchings at 2 A/250 VAC 1

– Fuse Protection

2 A slow

Error indication relay

– Switching Capacity

2 A/250 VAC 1(ohm)

– Fuse Protection

2 A slow

Indicators

– Operation

– Safety Stop

– Sensor / System Error

LED 5 mm

Green (Type ESR-31 built into reset button)

Yellow

Red

Reaction Time

Sensor 

Signal output relay < 70 ms (If external auxillary 

con tactors are controlled, the reaction time increases  

according to their drop-out time, normally 100 ms)

Temperature Range

– Operation –20°C to +50°C 

– Storage –20°C to +80°C

Humidity

max. 80% relative

Dimension Sheet

Periodic Tests

The correct function of the safety system is to be periodically checked (e.g. monthly or 

according to applicable national regulations). The sensors and their connections are to 

be inspected to determine possible mechanical damage. 

Once a year the sensor connecting cables are to be disconnected and checked accor-

ding to Commissioning points g) and h).

Start-up Test

A start-up test commences following activation of the “Reset” button or after interrup-

tion  of  the  power  supply  for  a  few  seconds.  This  test  should,  when  possible,  be  

vis ually verified.

Verification by means of LED’s:

– The error indication relay energises

– The red LED “System Error” illuminates for one second

– The red LED “Sensor Error” illuminates for one second

– Both yellow LED’s “Safety Function” illuminate for one second

–  Both yellow LED’s “Safety Function” and the green LED “Operation” blink for one 

second

–  Afterwards the green LED “Operation” illuminates to indicate the operating con-

dition and the signal output relays energise.

Technical data

74

36

12

74

85

Manufacturer: 

Bircher Reglomat AG, Wiesengasse 20, CH-8222 Beringen

Authorised rep 

Bircher Reglomat GmbH, Robert Bosch Strasse 3, D-71088 Holzgerlingen

Following directives  Manchinery directive 2006/42/EC, RoHS-Directive 2011/65/EU, 
have been observed:   Low Voltage Directive 2006/95/CE until 19.04.2016,  

Low Voltage Directive 2014/35/EU starting 20.04.2016
EMC-Directive 2004/108/EC until 19.04.2016,  
EMC-Directive 2014/30/EU starting 20.04.2016

EC type-examination  In combination with Safety Edges
certificate: 
Notified inspection  

Suva, Bereich Technik, SCESp 008, Kenn-Nr.1246 

centre: 
Signed: 

Head of Sales & Marketing Damian Grand /  
Head of Operations Daniel Nef

Product variants: 

ESR31C-24VDC, ESR32-24VDC, ESR32-115VAC, ESR32-230VAC