2

4.1

Value and parameter setting options

4.2

Basic functions of output relay status 

0

 (setting, see table 4.8)

4.3

Time functions 

1

, time unit 

2

 

and time factor 

 (settings, see table 4.8)

4.4

Sensitivity 

4

 (setting, see table 4.8)

4.5

Automatic sensitivity boost ASB 

S

 (setting, see table 4.8)

4.6

Frequency 

6

 (setting, see table 4.8)

4.7

Switching from operating to configuration mode

Standard display  

1-loop device

Standard display  

2-loop device

1

1 2

Explanation of the LEDs

Info

Red + Green

Start-up phase 

configuration

Green

Operation

Green 

flashing

Output 1 or / and 

activated

Flashing red

Error

Explanation of the LCD display

Loop 2

Loop 1

Function

Example:

 Time 

function set

1 2

Example:

Parameter 

“h” set

Parameter

Loop unactivated

Loop activated

Fault

1

Door and gate

2

Barrier

3

Quiescent 
current

Activation

 of the 

loop pulls the relay 

on; the relay drops 

off when the loop 

is exited.

t = typically ms or s

Switch-on delay:

When the loop is 

activated, the relay is 

pulled on after the time 

t

 

and drops off when the 

loop is exited.

t

t = typically ms or s

Switch-off delay:

When the loop is 

activated, the relay is 

pulled on drops off after 

time t 

t

 after the loop is 

exited.

t

t = typically ms or s

Activation pulse:

When the loop is 

activated, the relay 

is pulled on and 

drops back off 

after time 

t

.

t

t = typically ms or s

Exit pulse:

When the loop is exited, 

the relay is pulled on and 

drops back off after time 

t

.

t

t = typically ms or s

Maximum presence:

When the loop is 

activated, the relay is 

pulled on and drops back 

off when exited, but not 

later than after time 

t

.

t

t = typically ms or s

The sensitivity 

S

 of the loop detector can be adjusted in 9 steps: 

S1

 = lowest sensitivity 

(

 

much metal, low recognition distance)

S9

 = highest sensitivity

 (

➝ 

little metal, large recognition distance)

S4

 = factory setting

ASB

 (= 

A

utomatic 

S

ensitivity 

B

oost).  

ASB is required in order to be able to detect trailer drawbars after activation. 

Four different frequencies F1, F2, F3 and F4 can be set. This helps to prevent crosstalk with adjacent loops. Factory setting: F4. 

1-loop device

Display after 

start-up:

1

Touch the «Mode» button 

once to change to configura-

tion mode

Mode

1

2-loop device

Display after 

start-up:

1 2

Touch the «Mode» button 

once to change to configura-

tion mode

Mode

1

Loop 1 is 

selected

Mode

2

Loop 2 is selected 

(Back to automatic mode: Press and hold Mode button > 1 second)

Loop
Relay

Loop
Relay

Loop
Relay

Loop
Relay

Loop
Relay

Loop
Relay