Herkules

2

Microwave motion detector 

for industrial doors

1

Safety instructions

The unit may only be operated from a protection low-voltage
system with electrical separation. The unit may only be opened
and repaired by the supplier.
Never touch any electronic components of the detector

Translation of the original operation instruction

If  the  device  is  already  connected,  interrupt  the  power  supply  for
5 seconds.

After mounting, activate the wide field with the remote control (B+1).

IMPORTANT:

Fit the clip correctly!

Other addresses 5, 6 + 7 can be set using the remote control
(F+8+5…7)

Addressing

: Each detector can be assigned an address (1–4 with DIP

switch and 5–7 with remote control). Different addresses are neces-
sary when several detectors are within the range of a remote control.

– The detector must be firmly mounted on a flat surface. (Avoid

vibrations)

– Objects such as plants, flags, fans etc. must not protrude into

the detection area.

– The detector must not be obscured by covers/signs 
– Fluorescent lamps should not be placed in the immediate

vicinity of the detection area

– Mount the device in the middle above the industrial door

1. Affix drilling jig to wall or ceiling and drill holes according to values

given.

2. Route cable through opening provided in mounting bracket and

make sure length is sufficient for wiring.

3. Screw mounting bracket on tightly
4. Hook detector into mounting bracket and set detector to required

angle. Standard angle: 30°

5. Connect cable according to type plate.

3

Mounting

3.1

Before Mounting

3.2

Mechanical mounting

2

Description of the detector

*

 F

ac

to

ry

 s

et

tin

g

55 (2.17")

Ø 

5 (

0.2

")

73.5 (2.89")

13

.5

 (0

.5

3"

)

Herkules 2

Microwave motion detector
for industrial doors

TOP

TOP

4

5

3

7

6

9

1

2

5

8

13

12

14

15

10

11

Housing
Front cover
Rear wall
Mounting bracket
Fastening
Cover screws
8-pin cable
Microwave planar module
Screw terminal

1

2

3

4

5

6

7

8

Key 
Key 
Switch addressing
LED red
LED green
Clip

Y

X

9

10

11

12

13

15

14

1

2

3

4

5

Adress 1*

Adress 2

Adress 3

Adress 4

Wall mounting:

Ceiling mounting:

45

125

12

5

  5

0

 m

in

. 5

0

   

  4

1

45

12

5

125

  50

     41

 min. 50

Use the drilling jig enclosed
in the packaging!

Page 17

People/Vehicle Identification:

Choose whether differentiation

between people and vehicles is desired. If so, the minimum mounting
height of the sensor is 3 meters!

Field geometry: 

Select whether a narrow or wide field geometry

should be used. The clip must be used for the wide field.

Note:The clip can be used for mounting heights up to max. 4 m.

It is not mounted on delivery. (However, it is stuck onto the rear of the
antenna.)

E

N

G

LI

S

H

240334T

02/14

Summary of Contents for Herkules 2

Page 1: ...nom r ckvidden f r en fj rrstyrning Givaren m ste monteras p en plan yta Undvik vibrationer F rem l som v xter flaggor fl ktar osv f r inte komma in i detektorf ltet Givaren f r inte t ckas ver med lo...

Page 2: ...av str mf rs rjningen Med beh righetskod med fj rrstyrningen Idrifttagningsfas SMD Slow Motion Detection Minimala n stan statiska r relser detekteras s snart porten ppnar Den st ngs f rst n r ingen r...

Page 3: ...arn Alternativ 5 R2 Mot radarn R1 fr n radarn Alternativ 8 R2 Mot radarn R1 fr n radarn Alternativ 5 R2 mot radarn R1 fr n radarn Alternativ 1 R2 fordon R1 person Alternativ 1 R2 fordon R1 person Alte...

Page 4: ...n p separata utg ngar Standard port Reagerar endast p Fordon Standard port Reagerar endast p personer Standard port Personer och Fordon p samma utg ng Standard port Personer och Fordon En riktning per...

Page 5: ...av funktion Genom tryckning p knappen X Varje tryckning h jer v rdet med v rdet 1 Funktions nr N r den sista funktionen r n dd hoppar programmet ter till f rsta funktionen Gr n LED anger d numret p d...

Page 6: ...v rtrafik V rde 9 Porten ppnar vid tv rtrafik eller n rmanden fr n sidan Steg 1 Fj rrstyr ning Funktion Knappar C 1 Standard k nner av alla objekt P 1 1 C 2 Trafik rakt framifr n mot radarn alla objek...

Page 7: ...var koden fel B rja om vid 1 Tryck samtidigt knapparna X och Y under 8 sekunder Varannan sekund blinkar b da LED kort Apparaten r terst lld till fabriksinst llningarna Funktion Beh ringhetskod r fr n...

Page 8: ...0 14 mm2 Godk nnande CE 0682 FCC IC L nder EU EFTA US CA F ltm tt vid 30 lutning Fr n 2 5 m x 3 m BxD H jd 2 m Till 5 m x 7 m BxD H jd 7 m EG F rs kran om verenst mmelse Bircher Reglomat AG uppger h...

Page 9: ...dde af en fjernbetjening F leren skal fastmonteres p en plan flade Undg vibrationer Objekter som fx planter flag ventilatorer osv m ikke komme inden for registreringsfeltet F leren m ikke v re d kket...

Page 10: ...f leren x eller y at afbryde str mtilf rslen hj lp af adgangskoden og fjernbetjeningen Opstartsfase SMD Slow Motion Detection De mindste n sten um rkelige bev gelser registreres s snart porten bnes Re...

Page 11: ...af rel er Trin 5 R2 forl ns R1 bagl ns Trin 5 R2 forl ns R1 bagl ns Trin 8 R2 forl ns R1 bagl ns Trin 5 R2 forl ns R1 bagl ns Trin 1 R2 K ret j R1 person Trin 1 R2 K ret j R1 person Trin 6 R2 K ret j...

Page 12: ...soner k ret jer Standard port undertrykkelse af personer Standard port undertrykkelse af k ret jer Standard port personer k ret jer samme udgang Standard port personer k ret jer udgange retningsadskil...

Page 13: ...f leren Funktions ndring Ved tryk p knap X Pr tryk p knappen forh jes v rdien med 1 funkti onsnr N r den sidste funktion er n et springer programmet igen til den f rste funktion Den gr nne LED angive...

Page 14: ...afik Trin 9 Port bner ved krydsende trafik eller sidev rts tiln rmelse trin 1 Fjernbet jening Funktion Knapper C 1 Standard registrerer alle objekter P 1 1 C 2 Frontal trafik alle objekter P 1 2 C 3 H...

Page 15: ...og Y og hold dem nede i 8 sekunder Hvert 2 sekund lyser begge LED kort Enheden er tilbagestillet til fabriksindstilling Funktionen adgangskode er sl et fra Kode slettet Ny initialiserings og indl ring...

Page 16: ...lande EU EFTA US CA Feltdimensioner ved 30 h ldning fra 2 5 m x 3 m BxD h jde 2 m til 5 m x 7 m BxD h jde 7 m EU Overensstemmelseserkl ring Hermed erkl rer Bircher Reglomat AG at produktet Herkules op...

Page 17: ...oles according to values given 2 Route cable through opening provided in mounting bracket and make sure length is sufficient for wiring 3 Screw mounting bracket on tightly 4 Hook detector into mountin...

Page 18: ...tector x or y Interrupting electrical power supply Via access code on remote control Start up phase SMD Slow Motion Detection The slightest quasi static movements are detected as soon as the industria...

Page 19: ...backwards Level 5 R2 forwards R1 backwards Level 8 R2 forwards R1 backwards Level 5 R2 forwards R1 backwards Level 1 R2 Vehicle R1 Person Level 1 R2 Vehicle R1 Person Level 6 R2 Vehicle R1 Level 1 R2...

Page 20: ...hicles Standard industrial door people suppression Standard industrial door vehicle suppression Standard industrial door people and vehicles same output Standard industrial door people and vehicles ou...

Page 21: ...hanging the function Press key X The value increases by 1 for every key press function no Once the last function has been reached the program jumps back to the first function The green LED then indica...

Page 22: ...laterally level 1 Remote control Function Keys C 1 Standard detects all objects P 1 1 C 2 Frontal traffic all objects P 1 2 C 3 High speed industrial door all objects P 1 3 C 4 Detects slow movements...

Page 23: ...imultaneously and hold for 8 seconds Both LEDs light up briefly every 2 s Device is reset to factory settings Access code function is switched off Code deleted New initialisation and teach in phase st...

Page 24: ...m x 3 m WxD height 2 m to 5 m x 7 m WxD height 7 m EU Declaration of Conformity Bircher Reglomat AG herewith declares the product Herkules 2 to be in conformance with the basic requirements and other...

Reviews: