8
energized). This menu section is intended for the forced switching on and switching off
devices and units hooked up to the Controller.
Menu Functions:
а.) Screw: ON/OFF
This function allows switching on fuel supply in a forced manner for filling the screw
with fuel during its first start-up, clean-up, or check-up.
b.) Fan.
This function allows controlling fan operation with constant running capacity that is
set up in the User Menu with increments of 5% in the range of 0% to 100%.
c.) Central Heating Pump: ON/OFF
This function is intended for the forced switching on and switching off the pump,
check-up of its operability.
d.) Hot Water Supply Pump: ON/OFF
This function is intended for the forced switching on and switching off the pump,
check-up of its operability.
3.3.2 Firing:
ON/OFF
This function is intended for starting up the cold boiler. When activating this function
you transfer the boiler from «
Standby
» mode to «
Operation
» mode («
Standby
» mode was
activated due to temperature drop lower than the limit set up in Item 7.7).
3.3.3 Fan
І.
Pressurization Force
: 0 – 100%
This function controls fan operation efficiency. Adjustment limits are within the range
of 5% to 100% (conventionally it can be considered that these are steps of fan rpm).The
higher percent is the higher fan operation efficiency is.
ІІ.
Blow off
Blow off function is intended for removing accumulated gases from the combustion
chamber when the boiler is in support mode.
«
Blow off
» includes two values:
Pause
– frequency of fan switch on and
Operation
–
duration of fan operation.
а.) Pause: value change limits from 1 to 250 (min.)
b.) Operation: value change limits from 1 to 250 (sec.)