7
OUTLET INSTALLATION
1.
Insert the liner into the tank, ensuring holes line up between tank outlet and liner outlet.
2.
Insert 4” schedule 40 PVC pipe for use as an effluent line through tank into liner gasket until it hits the
baffle plate. Use a gasket, grout, mortar, or bituminous sealant (mastic) in the tank effluent hole for a
watertight seal between hole and effluent pipe.
CROSS BRACE
1.
Use the supplied stainless steel cross braces to secure the top of the unit to the tank wall to
prevent lateral movement.
2.
Use stainless steel hardware to mount the cross brace to the liner and the tank wall.