Loop-Powered Process Meter

DPM-400

www.binmaster.com

General

Environmental:

 

Operating temperature range:  

-40 to 75°C for safe area products

Storage temperature range:

 -40 to 85°C 

Relative humidity:

 0 to 90% non-condensing. Printed circuit boards are 

conformally coated.

Programming Method: 

Front panel & Free PC-based USB programming 

software

Enclosure & Materials:

 Enclosure: 1/8 DIN, IP65, NEMA 4X front panel, 

high impact plastic, NORYL

®

 polyphenylene ether & polystyrene blend 

(PPE PS) resin, UL 94V-0, Color: gray, Gasket: silicone rubber, Faceplate: 

LEXAN

®

 polycarbonate (PC) film, Buttons: silicone rubber

Noise Filter:

 Averages the input signal over a period of time between 1 

and 16 seconds to dampen the effects of a noisy signal that causes a 

jumpy display.

Filter Bypass:

 0.0 to 99.9% of full scale. Input signal changes greater 

than bypass value are displayed immediately.

Recalibration:

 Recalibration is recommended at least every 12 months. 

Max/Min Display: 

Max/min readings reached by the process are stored 

until reset by the user or until power to the meter is turned off. 

Tare: 

Zeros out display

Password: 

Programmable password restricts modification of programmed 

settings. 

Non-Volatile Memory:

 All programmed settings are stored in non-volatile 

memory for a minimum of ten years if power is lost. 

Normal Mode Rejection:

 64 dB at 50/60 Hz 

Connections:

 Removable screw terminals accept 12 to 22 AWG wire. 

DI Digital Input Contacts:

 2.1 VDC on contact. Connect normally open 

contacts across DI+ and DI-

DI Digital Input Logic Levels:

 Logic High: 2.4 to 30 VDC (max)  

Logic Low: 0 to 0.9 VDC 

Tightening Torque:

 

Screw terminal connectors:

 4.5 lb-in (0.5 Nm) 

Mounting screws:

 8.0 lb-in max. (0.9 Nm) 

Overall Dimensions: 

4.68" x 2.45" x 3.79" 

(119 mm x 62 mm x 96 mm) (W x H x D) 

weight:

 8.7 oz (247g) with option board 

warranty:

 3 years parts and labor

Common Open Collector & Relay (Alarm) 

Specifications

High or Low Alarm:

 User programmable for high or low alarm 

Alarm Deadband:

 0-100% FS, user programmable 

On & Off Time Delay:

 0 to 9,999 seconds 

Fail-Safe Operation:

 Independent for each open collector and relay

Fail-safe: 

on, the output is on under normal conditions

Fail-safe:

 off, the output is on under alarm conditions

Alarm Operation:

 Automatic, Automatic with manual override, Latching 

(manual reset anytime), Latching with reset after cleared (manual reset 

only after alarm has cleared)

Alarm Indication:

 Red backlight, flashing display, alarm symbol (!) 

(symbols not available on bargraph models) Bargraph segment flashes on 

alarm. 

Alarm Message:

 On or Off; User programmable, 8 characters maximum. 

Displayed every 10 seconds for 1 second on bottom line

Alarm Acknowledge:

 Front panel ACK button or external digital input 

resets output and screen indication

Auto Initialization: 

When power is applied to the meter, open collectors 

and relays will reflect the state of the input to the meter

Timer Output: 

One-shot or Continuous

Off Time Delay:

 1 sec to 99:59:59 (hrs:min:sec) 

On Time:

 1 sec to 99:59:59 (hrs:min:sec) 

Stopwatch:

 Output turns on when started and off when stopped

Open Collector Outputs

Rating: 

Two NPN, Isolated open collector, 30 VDC @ 150 mA max

Output Assignment: 

Pulse, Alarm, Timer, Stopwatch on/off, or Disable 

Pulse Output Source:

 PV (PV1, PV2) or Test Frequency 

Pulse Output Factor:

 0.000001 to 999,999.9 

Pulse width:

 0.5 ms @ 1 kHz; 500 ms @ 1 Hz; 50% duty cycle 

Pulse Output Frequency:

 1,000 Hz maximum 

Quadrature Pulse Output: 

Available for Output 2 (90° behind Output 1) 

Alarm Output Source:

 Assign to PV (PV1, PV2) or Digital Input

Solid State Relays

Rating: 

Resistive Load:

 250 VAC/DC @ 1 A

Inductive Load:

 75 VA @ 0.6 A, 250 VAC/DC max (Safe Area only)  

Noise Suppression:

 Metal oxide varistors across outputs 

Relay Assignment:

 Pump Alternation, Alarm, Timer, Stopwatch on/off, or 

Disable 

Alarm Output Source:

 Assign to PV (PV1, PV2) or Digital Input 

Pump Alternation:

 Relays will alternate with each pump cycle and 

alternation can be based on elapsed time. Pump alternation time can be 

programed for: 0 to 999:59 (hrs:min) 

Relay (Pump) Runtime:

 Meter will keep track of how long each relay 

(pump) has operated and display this information

Relay (Pump) Cycles:

 Meter will keep track of how many times the relays 

(pumps) have cycled and display this information 

4-20 mA Transmitter Output

Accuracy:

 ±0.05% FS ±0.001mA  

Output Source:

 PV1, PV2, re-transmit; reverse scaling allowed 

Scaling Range:

 1.00 to 23.0 mA 

Disable:

 High impedance state, less than 1 mA 

Calibration:

 Factory calibrated 4.00 to 20.00 mA 

Underrange:

 1.0 mA, 3.5 mA, or 3.8 mA (If input < 3.5 mA), or Off; user 

selectable 

Overrange:

 20.5 mA, 20.8 mA, or 23.0 mA (If input > 20.5 mA), or Off; 

user selectable 

Isolation:

 500 V input-to-output

Temperature Drift:

 0.5 μA/°C max from -40 to 75°C ambient 

External Loop Power Supply: 

7.0 VDC to 30.0 VDC maximum

Output Loop Resistance: 

10-750 Ω @ 24 VDC; 100-1100 Ω @ 30 VDC

Summary of Contents for DPM-400

Page 1: ...Safe Area Operating Temperature Range Free PC Based USB Programming Software 5 Digit Alphanumeric Top Line 8 Digit Alphanumeric Bottom Line Displays Level in Feet Inches up to 999 Feet 11 15 16 Inche...

Page 2: ...hese loop powered meters can be installed virtually anywhere because they get their power from the 4 20 mA loop and therefore require no separate power source And they only drop 1 5 V 4 7 V with backl...

Page 3: ...process is at certain DPM 400 models are available with a 20 segment bargraph This bargraph also includes a numeric value of the percentage the bargraph represents PV on the top line units and tag tog...

Page 4: ...and the relays are not available with pulse features The open collectors and relays can be controlled either automatically or manually The alarm status with flashing red message will show on the disp...

Page 5: ...mmodate under and over ranges from 1 to 23 mA The output can be reverse scaled such that the meter s high calibration value outputs 4 mA and the meter s low calibration outputs 20 mA PUMP CONTROL DPM...

Page 6: ...inputs for instance 0 0 and 2000 0 Round Horizontal Tank Linearization This function automatically calculates the volume in a round horizontal tank with flat ends Square Root Linearization The square...

Page 7: ...ow a 4 20 mA loop connected to the meter The first figure shows the connection without the backlight and the second shows the connection with the backlight The meter is powered by the 4 20 mA current...

Page 8: ...t Powered by 4 20 mA loop Intensity varies with signal level PD6603 BM Top line 99FT 11IN 15 16 to 999FT 11IN 15 16 Bottom line 8 digits 9 999 999 to 99 999 999 separated by commas or 8 characters all...

Page 9: ...set after cleared manual reset only after alarm has cleared Alarm Indication Red backlight flashing display alarm symbol symbols not available on bargraph models Bargraph segment flashes on alarm Alar...

Page 10: ...ed to The Relay Output window is used to assign a specific task to the 2 relays such as alarm sample timer stopwatch or off A custom message that will flash every 10 seconds can also be added The 4 20...

Page 11: ...Powered General Purpose Feet Inches Two Solid State Relays PD6603 L3N BM Loop Powered General Purpose Feet Inches 4 20 mA Analog Output PD6603 L5N BM Loop Powered General Purpose Feet Inches Two Solid...

Reviews: