9
Loop-Powered Process Meter
DPM-400
www.binmaster.com
General
Environmental:
Operating temperature range:
-40 to 75°C for safe area products
Storage temperature range:
-40 to 85°C
Relative humidity:
0 to 90% non-condensing. Printed circuit boards are
conformally coated.
Programming Method:
Front panel & Free PC-based USB programming
software
Enclosure & Materials:
Enclosure: 1/8 DIN, IP65, NEMA 4X front panel,
high impact plastic, NORYL
®
polyphenylene ether & polystyrene blend
(PPE PS) resin, UL 94V-0, Color: gray, Gasket: silicone rubber, Faceplate:
LEXAN
®
polycarbonate (PC) film, Buttons: silicone rubber
Noise Filter:
Averages the input signal over a period of time between 1
and 16 seconds to dampen the effects of a noisy signal that causes a
jumpy display.
Filter Bypass:
0.0 to 99.9% of full scale. Input signal changes greater
than bypass value are displayed immediately.
Recalibration:
Recalibration is recommended at least every 12 months.
Max/Min Display:
Max/min readings reached by the process are stored
until reset by the user or until power to the meter is turned off.
Tare:
Zeros out display
Password:
Programmable password restricts modification of programmed
settings.
Non-Volatile Memory:
All programmed settings are stored in non-volatile
memory for a minimum of ten years if power is lost.
Normal Mode Rejection:
64 dB at 50/60 Hz
Connections:
Removable screw terminals accept 12 to 22 AWG wire.
DI Digital Input Contacts:
2.1 VDC on contact. Connect normally open
contacts across DI+ and DI-
DI Digital Input Logic Levels:
Logic High: 2.4 to 30 VDC (max)
Logic Low: 0 to 0.9 VDC
Tightening Torque:
Screw terminal connectors:
4.5 lb-in (0.5 Nm)
Mounting screws:
8.0 lb-in max. (0.9 Nm)
Overall Dimensions:
4.68" x 2.45" x 3.79"
(119 mm x 62 mm x 96 mm) (W x H x D)
weight:
8.7 oz (247g) with option board
warranty:
3 years parts and labor
Common Open Collector & Relay (Alarm)
Specifications
High or Low Alarm:
User programmable for high or low alarm
Alarm Deadband:
0-100% FS, user programmable
On & Off Time Delay:
0 to 9,999 seconds
Fail-Safe Operation:
Independent for each open collector and relay
Fail-safe:
on, the output is on under normal conditions
Fail-safe:
off, the output is on under alarm conditions
Alarm Operation:
Automatic, Automatic with manual override, Latching
(manual reset anytime), Latching with reset after cleared (manual reset
only after alarm has cleared)
Alarm Indication:
Red backlight, flashing display, alarm symbol (!)
(symbols not available on bargraph models) Bargraph segment flashes on
alarm.
Alarm Message:
On or Off; User programmable, 8 characters maximum.
Displayed every 10 seconds for 1 second on bottom line
Alarm Acknowledge:
Front panel ACK button or external digital input
resets output and screen indication
Auto Initialization:
When power is applied to the meter, open collectors
and relays will reflect the state of the input to the meter
Timer Output:
One-shot or Continuous
Off Time Delay:
1 sec to 99:59:59 (hrs:min:sec)
On Time:
1 sec to 99:59:59 (hrs:min:sec)
Stopwatch:
Output turns on when started and off when stopped
Open Collector Outputs
Rating:
Two NPN, Isolated open collector, 30 VDC @ 150 mA max
Output Assignment:
Pulse, Alarm, Timer, Stopwatch on/off, or Disable
Pulse Output Source:
PV (PV1, PV2) or Test Frequency
Pulse Output Factor:
0.000001 to 999,999.9
Pulse width:
0.5 ms @ 1 kHz; 500 ms @ 1 Hz; 50% duty cycle
Pulse Output Frequency:
1,000 Hz maximum
Quadrature Pulse Output:
Available for Output 2 (90° behind Output 1)
Alarm Output Source:
Assign to PV (PV1, PV2) or Digital Input
Solid State Relays
Rating:
Resistive Load:
250 VAC/DC @ 1 A
Inductive Load:
75 VA @ 0.6 A, 250 VAC/DC max (Safe Area only)
Noise Suppression:
Metal oxide varistors across outputs
Relay Assignment:
Pump Alternation, Alarm, Timer, Stopwatch on/off, or
Disable
Alarm Output Source:
Assign to PV (PV1, PV2) or Digital Input
Pump Alternation:
Relays will alternate with each pump cycle and
alternation can be based on elapsed time. Pump alternation time can be
programed for: 0 to 999:59 (hrs:min)
Relay (Pump) Runtime:
Meter will keep track of how long each relay
(pump) has operated and display this information
Relay (Pump) Cycles:
Meter will keep track of how many times the relays
(pumps) have cycled and display this information
4-20 mA Transmitter Output
Accuracy:
±0.05% FS ±0.001mA
Output Source:
PV1, PV2, re-transmit; reverse scaling allowed
Scaling Range:
1.00 to 23.0 mA
Disable:
High impedance state, less than 1 mA
Calibration:
Factory calibrated 4.00 to 20.00 mA
Underrange:
1.0 mA, 3.5 mA, or 3.8 mA (If input < 3.5 mA), or Off; user
selectable
Overrange:
20.5 mA, 20.8 mA, or 23.0 mA (If input > 20.5 mA), or Off;
user selectable
Isolation:
500 V input-to-output
Temperature Drift:
0.5 μA/°C max from -40 to 75°C ambient
External Loop Power Supply:
7.0 VDC to 30.0 VDC maximum
Output Loop Resistance:
10-750 Ω @ 24 VDC; 100-1100 Ω @ 30 VDC