Loop-Powered Process Meter

DPM-400

www.binmaster.com

Password Protection

A password can be set for programming security to prevent unauthorized 

changes to the programmed parameter settings.

Input 1 is set to 4 mA

Display 1 is set to 0.0

EASY PROGRAMMING AND SETUP  

DPM-400s can be programmed and setup either by using the front panel 

buttons or free, PC-based software with USB interface.

Front Panel Buttons for Easy Setup, Programming, 

and Other Functions

DPM-400 process meters include four front panel buttons 

for setup and programming. The front panel buttons along 

with the dual-line display makes the DPM-400 easy to set 

up & program. Three of these buttons are also function 

keys that can be programmed to trigger certain events 

(i.e. acknowledge alarms, reset max and/or min, disable/

enable output relays, or hold current relay states), provide 

direct menu access points, and more.

One feature that makes the DPM-400s particularly easy to 

set up and program is that they can be scaled without ap-

plying a calibrated or known input. The user simply enters 

the desired values for Input 1 and Input 2 (for instance 4.000 and 20.00 

mA) and the corresponding display values for these inputs (for instance 

0.0 and 2000.0)

Round Horizontal Tank Linearization 

This function automatically calculates the volume in a round horizontal 

tank with flat ends. 

Square Root Linearization

The square root function can be used 

to linearize the signal from a differen-

tial pressure transmitter and display 

flow rate in engineering units.

Multi-Point Linearization

Meters are set up at the factory for linear function with 2-point linear-

ization. Up to 32 linearization points can be selected for the scaled 

value under the linear function. Multi-point linearization can be used to 

linearize the display for non-linear signals to convert level to flow using 

weirs and flumes with complex exponent.

Programmable Exponent Linearization 

The programmable exponent can be used to linearize the signal from 

level transmitters in open-channel flow applications using weirs and 

flumes.

FLOW

SIGNAL INPUT CONDITIONING

To satisfy applications that require scaling in ways other than the usual 

2-point linear method, the DPM-400 can also be scaled for square 

root (DP flow), programmable exponent (open channel flow) or round 

horizontal tank volume calculation.  

Loop-Powered Isolator for General Purpose Areas

The DPM-400 can be used as a loop-powered isolator for the 4-20 

mA signal in general purpose areas with the added benefit of a digital 

readout to display the process variable.

Summary of Contents for DPM-400

Page 1: ...Safe Area Operating Temperature Range Free PC Based USB Programming Software 5 Digit Alphanumeric Top Line 8 Digit Alphanumeric Bottom Line Displays Level in Feet Inches up to 999 Feet 11 15 16 Inche...

Page 2: ...hese loop powered meters can be installed virtually anywhere because they get their power from the 4 20 mA loop and therefore require no separate power source And they only drop 1 5 V 4 7 V with backl...

Page 3: ...process is at certain DPM 400 models are available with a 20 segment bargraph This bargraph also includes a numeric value of the percentage the bargraph represents PV on the top line units and tag tog...

Page 4: ...and the relays are not available with pulse features The open collectors and relays can be controlled either automatically or manually The alarm status with flashing red message will show on the disp...

Page 5: ...mmodate under and over ranges from 1 to 23 mA The output can be reverse scaled such that the meter s high calibration value outputs 4 mA and the meter s low calibration outputs 20 mA PUMP CONTROL DPM...

Page 6: ...inputs for instance 0 0 and 2000 0 Round Horizontal Tank Linearization This function automatically calculates the volume in a round horizontal tank with flat ends Square Root Linearization The square...

Page 7: ...ow a 4 20 mA loop connected to the meter The first figure shows the connection without the backlight and the second shows the connection with the backlight The meter is powered by the 4 20 mA current...

Page 8: ...t Powered by 4 20 mA loop Intensity varies with signal level PD6603 BM Top line 99FT 11IN 15 16 to 999FT 11IN 15 16 Bottom line 8 digits 9 999 999 to 99 999 999 separated by commas or 8 characters all...

Page 9: ...set after cleared manual reset only after alarm has cleared Alarm Indication Red backlight flashing display alarm symbol symbols not available on bargraph models Bargraph segment flashes on alarm Alar...

Page 10: ...ed to The Relay Output window is used to assign a specific task to the 2 relays such as alarm sample timer stopwatch or off A custom message that will flash every 10 seconds can also be added The 4 20...

Page 11: ...Powered General Purpose Feet Inches Two Solid State Relays PD6603 L3N BM Loop Powered General Purpose Feet Inches 4 20 mA Analog Output PD6603 L5N BM Loop Powered General Purpose Feet Inches Two Solid...