BINMASTER DPM-400 Manual Download Page 5

5

Loop-Powered Process Meter

DPM-400

www.binmaster.com

Timer Function Application

Application Timers are used in everyday life; one of the most common 

examples is the microwave oven. Industrial timers are used in process 

control applications where certain events or actions need to be controlled 

by time. Examples include automatic and batch control applications, 

where the relay needs to be energized for a specific length of time.
The timer fuction is available on the open collector and relay outputs; 

which means that you can have up to four timers per meter. The start 

and stop actions can be triggered from the setup menu or by the function 

keys and digital input. The meter can be setup to display the off/on timer 

count down.
There are two modes of operation:

1. Continuous Timer (Interval)

At the start of the timer the output is off and turns on after the 

Off Delay elapses. The output remains on for the duration of the 

On Time. The cycle repeats until the user stops the timer either from 

the menu or a function key.

2. One-Shot Timer

At the start of the timer the output is off and turns on after the  

Off Delay elapses. The output remains on for the duration of the  

On Time. The timer stops and the cycle does not repeat.

Optional Isolated 4-20 mA Output

The isolated analog output signal can be configured to represent the 

process variable (PV1, PV2, or retransmit). While the output is nominally 

4-20 mA, the signal will accurately accommodate under- and over-

ranges from 1 to 23 mA. The output can be reverse scaled such that 

the meter’s high calibration value outputs 4 mA and the meter’s low 

calibration outputs 20 mA.

PUMP CONTROL

DPM-400s, when ordered with the two solid state relays, have several 

features that make them ideal for simple duplex pump control. The 

relays can be programmed to alternate the pumps based on level and 

runtime thus ensuring even wear on both pumps. If the level remains 

constant (within on/off points), alternation is based on runtime. If the 

level cycles the on/off points, alternation is based on level and runtime. 

If the run time is set to 0, alternation is based on level. The meter also 

keeps track of runtime for both pumps and the number of times they 

have cycled.   

Display Pump Runtime & Cycle Count

In addition to the two solid state relays for controlling pumps, the  

DPM-400s two open collectors could be used to indicate high or low level 

alarm conditions.

Pump Alternation Application 

The DPM-400 can be used as a pump controller to alternate two 

pumps and provide high and low level alarm indication. The pumps can 

be programmed to alternate on level and run time and the meter can 

display the pump run times and the number of times they have cycled. 

The meter can display the number 

of times the relays have cycled

The meter can display pump 

runtime for both pumps  

a.

  A sensor detects the bottle is in place and 

triggers the digital input to start the timer

b.

 The timer output controls the filling pump

c.

  The On Time is set according to the time 

needed to fill the bottle

NEw FEATURE:

 

DPM-400 displays pump runtime and number of cycles.

Summary of Contents for DPM-400

Page 1: ...Safe Area Operating Temperature Range Free PC Based USB Programming Software 5 Digit Alphanumeric Top Line 8 Digit Alphanumeric Bottom Line Displays Level in Feet Inches up to 999 Feet 11 15 16 Inche...

Page 2: ...hese loop powered meters can be installed virtually anywhere because they get their power from the 4 20 mA loop and therefore require no separate power source And they only drop 1 5 V 4 7 V with backl...

Page 3: ...process is at certain DPM 400 models are available with a 20 segment bargraph This bargraph also includes a numeric value of the percentage the bargraph represents PV on the top line units and tag tog...

Page 4: ...and the relays are not available with pulse features The open collectors and relays can be controlled either automatically or manually The alarm status with flashing red message will show on the disp...

Page 5: ...mmodate under and over ranges from 1 to 23 mA The output can be reverse scaled such that the meter s high calibration value outputs 4 mA and the meter s low calibration outputs 20 mA PUMP CONTROL DPM...

Page 6: ...inputs for instance 0 0 and 2000 0 Round Horizontal Tank Linearization This function automatically calculates the volume in a round horizontal tank with flat ends Square Root Linearization The square...

Page 7: ...ow a 4 20 mA loop connected to the meter The first figure shows the connection without the backlight and the second shows the connection with the backlight The meter is powered by the 4 20 mA current...

Page 8: ...t Powered by 4 20 mA loop Intensity varies with signal level PD6603 BM Top line 99FT 11IN 15 16 to 999FT 11IN 15 16 Bottom line 8 digits 9 999 999 to 99 999 999 separated by commas or 8 characters all...

Page 9: ...set after cleared manual reset only after alarm has cleared Alarm Indication Red backlight flashing display alarm symbol symbols not available on bargraph models Bargraph segment flashes on alarm Alar...

Page 10: ...ed to The Relay Output window is used to assign a specific task to the 2 relays such as alarm sample timer stopwatch or off A custom message that will flash every 10 seconds can also be added The 4 20...

Page 11: ...Powered General Purpose Feet Inches Two Solid State Relays PD6603 L3N BM Loop Powered General Purpose Feet Inches 4 20 mA Analog Output PD6603 L5N BM Loop Powered General Purpose Feet Inches Two Solid...

Reviews: